Daikin EKHBH030BA Operation Manual page 14

Indoor unit for air to water heat pump system and options
Hide thumbs Also See for EKHBH030BA:
Table of Contents

Advertisement

Available languages

Available languages

[1] Weather dependent set point (heating operation only)
The weather dependent set point field settings define the parameters
for the weather dependent operation of the unit. When weather
dependent operation is active the water temperature is determined
automatically depending on the outdoor temperature: colder outdoor
temperatures will result in warmer water and vice versa. During
weather dependent operation, the user has the possibility to shift up
or down the target water temperature by a maximum of 9°F (5°C).
[1-00] Low ambient temperature (Lo_A): low outdoor
temperature.
[1-01] High ambient temperature (Hi_A): high outdoor
temperature.
[1-02] Set point at low ambient temperature (Lo_Ti): the
target outgoing water temperature when the outdoor
temperature equals or drops below the low ambient
temperature (Lo_A).
Note that the Lo_Ti value should be higher than Hi_Ti, as for
colder outdoor temperatures (i.e. Lo_A) warmer water is
required.
[1-03] Set point at high ambient temperature (Hi_Ti): the
target outgoing water temperature when the outdoor
temperature equals or rises above the high ambient
temperature (Hi_A).
Note that the Hi_Ti value should be lower than Lo_Ti, as for
warmer outdoor temperatures (i.e. Hi_A) less warm water
suffices.
T
t
Lo_Ti
Hi_Ti
Lo_A
T
Target water temperature
t
T
Ambient (outdoor) temperature
A
Shift value
= Shift value
Following table shows relation between displayed shift value and
actual used shift value.
Display
°C
°F
5
9.0
5 5 5 5
4
7.2
4 4 4 4
3
5.4
3 3 3 3
2
3.6
2 2 2 2
1
1.8
1 1 1 1
empty
0
0
–1
–1.8
– – – – 1 1 1 1
–2
–3.6
– – – – 2 2 2 2
–3
–5.4
– – – – 3 3 3 3
–4
–7.2
– – – – 4 4 4 4
–5
–9.0
– – – – 5 5 5 5
Operation manual
13
+9.0°F (+5°C)
0
Shift value
–9.0°F(–5°C)
Hi_A
T
A
[2] Disinfection function
Applies only to installations with a domestic hot water tank.
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function field settings must be configured
by the installer according to local laws and regulations.
[2-00] Operation interval: day(s) of the week at which the
domestic hot water should be heated.
[2-01] Status: defines whether the disinfection function is
turned on (1) or off (0).
[2-02] Start time: time of the day at which the domestic hot
water should be heated.
[2-03] Set point: high water temperature to be reached.
[2-04] Interval: time period defining how long the set point
temperature should be maintained.
T
DHW
[2-03]
T
H
T
U
00.00
01.00
T
Domestic hot water temperature
DHW
T
User set point temperature (as set on the user interface)
U
T
High set point temperature [2-03]
H
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
If this high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to local laws and regulations.
Indoor unit for air to water heat pump system and options
[2-04]
22.00
23.00
24.00
t
[2-02]
EKHBH/X030BA
4PW62569-1 – 07.2010

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ekhbx030ba

Table of Contents