Power Supply Specifications; Environmental Specifications; Table 24. Power Supply Specifications; Table 25. Environmental Specifications - Dell PowerEdge R520 Technical Manual

Two-socket, 2u rack server
Hide thumbs Also See for PowerEdge R520:
Table of Contents

Advertisement

Power supply specifications

Table 24 lists power supply specifications for the PowerEdge R520.
Specification
Current
consumption
Supply voltage
100–240VAC
Frequency
Heat dissipation
(BTU/hr max)
Maximum inrush
2
current
1
Auto-ranging
2
Under typical line conditions and over the entire system ambient operating range, the inrush current may reach 55A per
power supply for 10ms or less.

Environmental specifications

Table 25 details the environmental specifications for the R520. For additional information about
environmental measurements for specific system configurations, see
Dell.com/environmental_datasheets.
Fresh Air: temperature, humidity, altitude de-rating
Continuous
10°C to 35°C (50°F to 95°F) at 10% to 80% relative humidity with 26°C (78.8°F) maximum
operation
dew point (maximum wet bulb temperature). De-rate maximum allowable dry bulb
temperature at 1°C per 300m above 950m (1°F per 547 ft above 3117 ft).
Expanded
When operating in the expanded temperature range, system performance may be impacted
operation
and ambient temperature warnings may be reported on the LCD and in the System Event
Log.
≤ 10% of annual operating hours: 5°C to 10°C and 35°C to 40°C (with no direct sunlight on
the equipment) at 5% to 85% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to 5°C or up to 40°C for a maximum of 10% of its annual operating hours. For
temperatures between 35°C and 40°C (95°F to 104°F), de-rate maximum allowable dry bulb
temperature by 1°C per 175m above 950m (1°F per 319 ft above 3117 ft).
≤ 1% of annual operating hours: –5°C to 5°C and 40°C to 45°C (with no direct sunlight on
the equipment) at 5% to 90% relative humidity with 26°C dew point (maximum wet bulb
temperature). Outside the standard operating temperature (10°C to 35°C), the system can
operate down to –5°C or up to 45°C for a maximum of 1% of its annual operating hours. For
temperatures between 40°C and 45°C (104°F to 113°F), de-rate maximum allowable dry bulb
temperature by 1°C per 125m above 950m (1°F per 228 ft above 3117 ft).
Expanded operation restrictions:
45
PowerEdge R520 Technical Guide
Table 24.
Power supply specifications
495W AC
550W AC
6.5–3A
7.4–3.7A
1
100–240VAC
50/60Hz
50/60Hz
1908
2315
55A
55A
Table 25.
Environmental specifications
System must have six fans
Processors not supported: 130W, 4-core processors, 135W processors, Intel Core
processors
750W AC
750W AC
Titanium
Platinum
10–5A
10–5A
1
200–240VAC 100–240VAC
50/60Hz
50/60Hz
2843
2891
55A
55A
1100W AC
1100W DC
12–6.5A
32A
-48V to -60
1
1
100–240VAC
VDC
50/60Hz
N/A
4100
4416
55A
55A