Summary of Contents for Goodman IO-367B
Page 1
All information contained herein is subject to change without notice. These installation instructions cover the outdoor installation of single package electric heating and cooling units. See the Specification Sheet applicable to your model for information regarding accessories. IO-367B 7/10 NSTRUCTIONS OMMERCIAL & C EATING 15 &...
WARNING O PREVENT THE RISK OF PROPERTY DAMAGE, PERSONAL INJURY, OR DEATH, DO NOT STORE COMBUSTIBLE MATERIALS OR USE GASOLINE OR OTHER FLAMMABLE LIQUIDS OR VAPORS IN THE VICINITY OF THIS APPLIANCE. WARNING HIGH VOLTAGE! NSTALLATION REPAIR THIS...
UNIT LOCATION WARNING O PREVENT POSSIBLE EQUIPMENT DAMAGE PERSONAL INJURY OR DEATH THE FOLLOWING BULLET POINTS MUST BE OBSERVED WHEN INSTALLING THE UNIT IMPORTANT NOTE: Remove wood shipping rails prior to installation of the unit. See important note under Roof Curb Installation Only.
Page 5
• Do not skid or slide on any surface as this may damage unit base. The unit must be stored on a flat, level surface. Protect the condenser coil because it is easily damaged. NSTALLATIONS Before installing this unit... IMPORTANT NOTE: This unit has been equipped with a ship- ping brace under the compressor section that MUST BE RE- MOVED before installing the unit on a roof curb.
CAUTION LL CURBS LOOK SIMILAR O AVOID INCORRECT CURB POSITIONING CHECK JOB PLANS CAREFULLY AND VERIFY MARKINGS ON CURB ASSEMBLY NSTRUCTIONS MAY VARY IN CURB STYLES AND SUPERSEDES INFORMATION SHOWN See the manual shipped with the roof curb for assembly and installation instructions.
RIGGING DETAILS WARNING O PREVENT PROPERTY DAMAGE, THE UNIT SHOULD REMAIN IN AN UPRIGHT POSITION DURING ALL RIGGING AND MOVING OPERATIONS. LIFTING AND MOVING WHEN A CRANE IS USED, PLACE THE UNIT IN AN ADEQUATE CABLE SLING. CAUTION O NOT LIFT UNITS TWO AT A TIME ROVISIONS FOR FORKS HAVE BEEN INCLUDED IN THE UNIT BASE FRAME 72”...
CPC Weights (lbs) DATA 15 Tons Corner Weight - A Corner Weight - B Corner Weight - C Corner Weight - D Unit Shipping Weight 2150 Unit Operating Weight 2035 X (Inches) 60" 43" Y (Inches) NOTE: These weights are without accessories installed. CAUTION O PREVENT SEVERE DAMAGE TO THE BOTTOM OF THE UNIT FORK LIFT UNIT AFTER WOOD STRUTS HAVE BEEN REMOVED...
Page 9
CAUTION O AVOID PROPERTY DAMAGE OR PERSONAL INJURY DUE TO FIRE, USE ONLY COPPER CONDUCTORS. CAUTION ABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS IRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION ERIFY PROPER OPERATION AFTER SERVICING NOTE: A weather-tight disconnect switch, properly sized for the unit total load, must be field installed.
3. Use #18 AWG wire for 24V control wiring runs not exceeding 75 feet. Use #16 AWG wire for 24V control wiring runs not exceeding 125 feet. Use #14 AWG wire for 24V control wiring runs not exceeding 200 feet. Low voltage wiring may be National Electrical Code (NEC) Class 2 where permitted by local codes.
Page 11
TARTUP NSTRUCTIONS CAUTION O PREVENT PROPERTY DAMAGE OR PERSONAL INJURY START THE UNIT UNTIL ALL NECESSARY PRE HAVE BEEN PERFORMED Prior to the beginning of Startup, Adjustments, and Checks procedures, the following steps should be completed in the building. THERMOSTAT. Set the thermostat in the conditioned space at a point at least 10°F below zone temperature.
Page 12
System Voltage - That nominal voltage value assigned to a circuit or system for the purpose of designating its voltage class. Nameplate Voltage - That voltage assigned to a piece of equipment for the purpose of designating its voltage class and for the purpose of defining the minimum and maximum voltage at which the equipment will operate.
EFRIGERATION YSTEM HECKS Ensure the hold-down bolts on the compressor are secure and have not vibrated loose during shipment. Check that vi- bration grommets have been installed. Visually check all pip- ing and clamps. The entire refrigeration system has been factory charged and tested, making it unnecessary to field charge.
HEET METAL PARTS HAVE SHARP EDGES SERVICE PERSONNEL EXERCISE CAUTION Your Self Contained Packaged Air Conditioner and Heat Pump should operate for many years without excessive service calls if the unit is installed properly. However it is recommended that the homeowner inspect the unit before a seasonal start up.
LEAN UTSIDE UALIFIED The coil with the outside air flowing over it should be inspected annually and cleaned as frequently as necessary to keep the finned areas free of lint, hair and debris. ONDENSER VAPORATOR NDUCED Bearings on the air circulating blower motor, condenser mo- tor and the combustion fan motor are permanently lubricated.
APPENDIX A BLOWER PERFORMANCE DATA CPC180 STANDARD BELT DRIVE ESP, In H 7477 7112 2.96 6467 5983 2.38 5190 4426 1.71 CPC240 STANDARD BELT DRIVE ESP, In H 8171 7901 7344 4.35 NOTES: High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model. Unit factory shipped with sheave set at 2.5 turns open.
APPENDIX A BLOWER PERFORMANCE DATA CPC180 HIGH STATIC BELT DRIVE ESP, In H 6419 6261 4.01 CPC240 HIGH STATIC BELT DRIVE ESP, In H 8209 7967 6.02 6883 6594 4.87 NOTES: High static airflow requires installation of high static kit (HSKT240), or factory-built High Static model. Unit factory shipped with sheave set at 2.5 turns open.
VOLTAGE LIMITATIONS VOLTAGE MODELS (NAMEPLATE) 208/230-60-3 15 TON 460-60-3 575-60-3 VOLTAGE LIMITATIONS MODELS (NAMEPLATE) 208/230-60-3 20 TON 460-60-3 575-60-3 NOTE: See unit nameplate for proper overcurrent protection. HEATER KIT MINIMUM CFM UNIT MODEL NUMBER EHK3-31 15 TON EHK3-46 EHK3-60 EHK3-31 20 TON EHK3-46 EHK3-60...