Cable Connection; Connecting Input Plug And Loads; Connecting Battery Cables; Table 2 Input Circuit Breaker Specification - Liebert GXT3 User Manual

120v/208v 500va-3000va
Hide thumbs Also See for GXT3:
Table of Contents

Advertisement

2.5

Cable Connection

®
The Liebert
GXT3
(Output cables are on GXT3-3000 models only). Refer to 1.3.2 - Rear Panel Features for details.
The battery cables are supplied with the battery cabinet.
2.5.1

Connecting Input Plug and Loads

NOTE
Ensure that all the loads are turned Off.
Prepare an input power supply that is properly protected by a circuit breaker in accordance
with national and local electrical codes. The wall receptacle must be grounded.
The plug on the power supply cord is intended to serve as the disconnect device. The
socket-outlet must be installed near the equipment and must be easily accessible.
Emerson recommends installing an upstream circuit breaker of the same series as the Liebert
GXT3's input circuit breaker.
The specification of input circuit breaker on the rear panel of UPS is given in Table 2.
Table 2
Input circuit breaker specification
Model
GXT3-500RT120
GXT3-700RT120
GXT3-1000RT120
GXT3-1000MT120
GXT3-1500RT120
GXT3-2000RT120
GXT3-3000RT120
GXT3-3000RT208
1. Plug all loads into the output receptacles on the rear panel of the Liebert GXT3.
NOTE
1. Distribute loads evenly across all receptacles to prevent overloading individual receptacles.
2. Output cable length should not exceed 32.8 ft (10m).
3. Insert the input plug of Liebert GXT3 into the input power connection.
2.5.2

Connecting Battery Cables

1. Switch Off the input breaker of the battery cabinet.
2. Take out the battery cable included with the battery cabinet.
3. Connect one end of the battery cable to the external battery connector on the rear panel of the
UPS, and connect the other end to any battery port on the rear panel of the battery cabinet.
4. Switch On the battery breaker on the rear of the external battery cabinet.
5. Use the Configuration Program included with the UPS to specify the number of external battery
cabinets connected to the Liebert GXT3. See Table 15 for approximate battery run times.
rear panel has an input cable and plug, output receptacles and output cable(s)
Rated Circuit
Breaker
8A
10A
15A
15A
15A
20A
30A
20A
17
Installation

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents