2: Command 08-Diagnostic; 3: Command 11-Get Com Event Counter - Honeywell XYR 5000 Series User Manual

Wireless base radio
Hide thumbs Also See for XYR 5000 Series:
Table of Contents

Advertisement

Honeywell Industrial Wireless
6.3.2: Command 08- Diagnostic
6.3.3: Command 11-
Get Com Event Counter
20 Rev. 3
11/04
This command provides a number of tests for checking the communica-
tions between the Base Radio and the Host master device.
Sub-function
Code
Transmitter Device Status
0 Return Query Data
1 Restart Communications Option
2 Return Diagnostics Register
Change ASC-II Input Delimiter (NOT
3
SUPPORTED)
4 Force Listen Only Mode
5-9 NOT USED
10 Clear Counters & Diagnostics Register
11 Return Bus Message Count
12 Return Bus Communication Error
13 Return Bus Exception Error Count
14 Return Slave Message Count
15 Return Slave No Response Count
16 Return Slave NAK Count
17 Return Slave Busy Count
18 Return Bus Character Overrun Count
19+ NOT USED
Note that identical information is returned for any device ID that the Base
Radio has control of (i.e. including Transmitters mapped to virtual device
IDs when operating in the device ID mapping mode (See Section 6.2).
This command returns a two -byte status word and the device's event
counter. The status word will either be 0 or 65535 if the previous com-
mand is still being processed. The event counter is incremented for each
successful message received. The counter is not incremented for com-
mands that return exception responses or commands that fetch event
counters. The event counter will eventually roll over to 0 after reaching a
count of 65535. Note that identical information is returned for any device
ID that the Base Radio has control of (i.e. including Transmitters mapped
to virtual device IDs when operating in the device ID mapping mode).
For further details on this command, please consult the Modbus protocol
specification.