Overall Configuration Menu Map; The Number Of Wireless Instruments Setting (Num Wi); Setting The User Password; Menu Map To Number Of Wireless Instruments Setting - Honeywell XYR 5000 Series User Manual

Wireless base radio
Hide thumbs Also See for XYR 5000 Series:
Table of Contents

Advertisement

Honeywell Industrial Wireless
4.2: Overall Configuration
Menu Map
NOTE
The user must enter a four digit password to enter
the CONFIG and DIAGNSE. The FACTORY
menu is for factory use only. The default user
password is 0000. For more information on the
password see Section 4.4.
4.3: The Number of Wireless
4.3: The Number of Wireless
Instruments Setting
Instruments Setting
Figure 4.4: Menu Map to Number of
Wireless Instruments Setting

4.4: Setting the User Password

Figure 4.5: Menu Map to Password
Setting
Rev. 3
11/04
A complete Base Radio Menu Map is shown in Appendix B. Below is an
overall view of the configuration menu to aid the user in setting up the
Base Radio for proper operation.
Figure 4.3: Overall Configuration Menu Map
The Number of Wireless Instruments setup allows you to track Transmit-
ter communication. By indicating the number of Transmitters allotted to
that particular Base Radio, the Base Radio can judge whether or not it is
missing communication with a Transmitter and then warn the user.
For example, if you had 10 Transmitters to be set to this Base Radio, you
would set the number of wireless instruments to 10. When you returned to
the operations sequence you would then read "BASE OK" and "10 WI" if
all the Transmitters were in communication with the Base Radio. If one
Transmitter was not in communication with the Base Radio, you would
read "MIS 1" and "9 WI" for the 1 missing Transmitter.
Follow the Base Radio menu map shown to the left in Figure 4.4 to con-
figure the number of wireless instruments (Transmitters). The factory de-
fault is 001. There is a limit of 50 Transmitters per Base Radio.
Each Base Radio has a password that will lock out undesired users from
making changes to the Base Radio. Any user may still view some of the
Base Radio settings by pressing the ENTER key during the Operations
Sequence and viewing the Read Only Sequence.
The password is a four-digit password. The factory default is 0000. If you
wish to select a different password, follow the Base Radio Menu Map
shown in Figure 4.5 to change it.
If you forget your password you must call your Honeywell Sales Repre-
sentative to have it reset.