Analog Value Object - Honeywell BacNet protocol Installation And User Manual

For variable frequency drives
Table of Contents

Advertisement

Honeywell • 29
6.1.2

Analog Value Object

Instance ID
Object Name
AV0
Frequency Setpoint
AV1
Output Frequency
AV2
Motor Speed
AV3
Load (power)
AV4
Kilowatt Hours total
AV5
Motor Current
AV6
DC link Voltage
AV7
Motor Voltage
AV8
Unit Temperature
AV9
Motor Torque
AV10
Operating Days
AV11
Operating Hours
AV12
Kilowatt Hours
AV13
Torque Reference
AV14
Temperature Rise
AV15
fb_ProcessdataOut_01
AV16
fb_ProcessdataOut_02
AV17
fb_ProcessdataOut_03
AV18
fb_ProcessdataOut_04
AV19
fb_ProcessdataOut_05
AV20
fb_ProcessdataOut_06
AV21
fb_ProcessdataOut_07
AV22
fb_ProcessdataOut_08
AV23
Active Fault Code
AV24
Speed Reference
AV25
Current Limit
AV26
Min Frequency
Description
Frequency Setpoint
Output Frequency
Motor Speed
Motor Shaft Power
Kilowatt Hour Counter
(Total)
Motor Current
DC link Voltage
Motor Voltage
Heatsink Temperature
In % of motor nominal
Torque
Operating Days (reset-
table)
Operating Hours (reset-
table)
Kilowatt Hours (resetta-
ble)
Torque Reference
Calculated motor tem-
perature 100,0% = nom-
inal temperature of
motor
Application specific
Application specific
Application specific
Application specific
Application specific
Application specific
Application specific
Application specific
Active Fault Code
Speed Reference, per-
centage of nominal
speed
Current Limit
Minimum Frequency
Communications
Present Value
Units
Access Type
Hz
Hz
rpm
%
kWh
A
V
V
C
%
Day
Hour
kWh
%
%
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
16 bit Resolution 1
-
%
A
Hz
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
C
W
W

Hide quick links: