Honeywell • 27
6.1.1

Binary Value Object

Instance
ID
BV0
Ready State
BV1
Run/Stop State
BV2
Fwd/Rev State
BV3
Fault State
BV4
Alarm State
BV5
At Setpoint
BV6
At Zero Speed
BV7
fb_ProcessdataOut_01 Bit_0
BV8
fb_ProcessdataOut_01 Bit_1
BV9
fb_ProcessdataOut_01 Bit_2
BV10
fb_ProcessdataOut_01 Bit_3
BV11
fb_ProcessdataOut_01 Bit_4
BV12
fb_ProcessdataOut_01 Bit_5
BV13
fb_ProcessdataOut_01 Bit_6
BV14
fb_ProcessdataOut_01 Bit_7
BV15
Run/Stop CMD
BV16
Fwd/Rev
BV17
Reset Fault
BV18
Stop By Coast
BV19
Stop By Ramp
BV20
Quick Stop
BV21
Zero Ramp
BV22
Hold Ramp
BV23
BusCtrl
BV24
BusRef
BV25
fb_control_word Bit_10
BV26
fb_control_word Bit_11
BV27
fb_control_word Bit_12
Object Name
Description
Indicates whether the drive
is ready or not
Indicates whether the drive
is running or stopped
Indicates the rotation direc-
tion of the motor
Indicates if a fault is active
Indicates if an alarm is
active
Ref. Frequency reached
Motor Running at zero
speed
ProcessDataOut1 bit 0
ProcessDataOut1 bit 1
ProcessDataOut1 bit 2
ProcessDataOut1 bit 3
ProcessDataOut1 bit 4
ProcessDataOut1 bit 5
ProcessDataOut1 bit 6
ProcessDataOut1 bit 7
Command to start drive (FB
control is active)
Direction of motor
Command to reset Active
Fault from drive
Stop Drive by coast
Stop Drive by ramp
Quick Stop
Stop by zero ramp
Hold ramp
Activate Bus control
Activate Bus reference
fb_control_word bit 10
fb_control_word bit 11
fb_control_word bit 12
Communications
Present
Inactive /
Value
Active
Access
Type
Not Ready /
R
Ready
Stop / Run
R
Fwd / Rev
R
OK / Fault
R
OK / Alarm
R
False / True
R
False / True
R
0 / 1
R
0 / 1
R
0 / 1
R
0 / 1
R
0 / 1
R
0 / 1
R
0 / 1
R
0 / 1
R
Stop / Run
C
Fwd / Rev
C
0 / Reset
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C
0 / 1
C