Programming

5.
Programming
Basic information on how to use the control keypad you will find in the Application Manual.
The navigation path to the fieldbus parameters may differ from application to application. The
exemplary paths below apply to the Honeywell SmartDrive.
1. First ensure that the right fieldbus protocol is selected.
Navigate: Main Menu > I/O and Hardware (M5) > RS-485 (M5.7) OR Ethernet
(M5.8) > Common settings (M5.7.1) > Protocol (P5.7.1.1) > Edit >
(Choose protocol)
2. Select
'Fieldbus control'
Navigate: Main Menu > Quick Setup (M1) > Rem. Ctrl. Place (P1.15)
OR
Navigate: Main Menu > Parameters (M3) > Start/Stop Setup (M3.2) > Rem.
Ctrl. Place (P3.2.1)
3. Choose source of reference.
Navigate: Main Menu > Parameters (M3) > References (M3.3)
4. Set fieldbus parameters (M5.7 and M5.8). See below.
5.1

BACnet MS/TP parameters and monitoring values (M5.7.3)

Code
Parameter
PARAMETERS
P5.7.3.1.1
Baud rate
P5.7.3.1.2
Autobauding
P5.7.3.1.3
MAC address
P5.7.3.1.4
Instance number
Communication
P5.7.3.1.5
time-out
as the
Remote Control Place
Min
Max
1
4
0
1
1
127
0
65535
0
65535
.
Unit
Default
ID
bd
1
1
1
0
s
10
Honeywell • 16
Description
Communication speed
1 = 9600
2 = 19200
3 = 38400
4 = 76800
Automatic baudrate
detection
0 = Off
1 = On; The automati-
cally detected baud rate
is then shown as value
of parameter P5.7.3.1.1
Device Object's instance
number.
0 = Automatically
gegerated
0 = Not used