6.2

EVENT SCREENS (Alarm)

Each of the following listed alarms or messages can be displayed on the LCD screen or transmitted to a
PC through the serial port RS232 or the SNMP card (optional).
Entering the Alarm mode, the LCD screen displays a sequence of screens corresponding to the last 256
alarms & events, each screen indicating:
01.06.2007
12:15:45
NR=255
Status=A588
4580: INVERTER AND
MAINS SYNCHRONIZED
6.2.1

Alarms list

Are defined alarms:
Code
Alarm
SETUP VALUES
4000
LOST
REGULATION BOARD
4001
FAILURE
UPS
4004
FAILURE
RECTIFIER FUSES
4100
FAILURE
K4 CLOSING
4102
FAILURE
K4 OPENING
4103
FAILURE
RECTIFIER MAINS
4110
OUT OF TOLERANCE
LOW BATTERY
4115
VOLTAGE
HIGH BATTERY
4116
VOLTAGE
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
1.
The exact date and time when the event occurred.
2.
The number (255 being the most recent) and status code.
3.
The software version implemented on control board and
explicit text description of the event.
all the events which activate the LED Warning (yellow) and the buzzer in order
to alert the user about an abnormal situation.
Parameters are lost and have been replaced with default
values.
Voltage supply +/-15 VDC has been detected out of tolerance
on the P1 – Control board or the programmable circuits are
defective.
The master unit detected the slave unit missing on the
communication bus even though switch Q1 is still closed.
The trip indicator mounted on rectifier input fuses indicates a
blown fuse.
The rectifier is turned Off (K4 open) and the load will be supplied
by the battery.
K4 not closed despite a closing command being done.
The rectifier is switched OFF.
K4 not open despite an opening command being done.
The rectifier is switched OFF.
Rectifier input mains has been detected out of tolerance
(voltage, frequency or phase).
The battery has been discharged and reached "stop operation"
time-out (default 3 minutes), the inverter will be shut down.
It restarts automatically only when the battery has recovered
energy to ensure min. a "stop operation" time to the actual
load.
Dangerous high UDC-Voltage.
Causes Inverter shutdown. Inverter restarts automatically after
return to normal floating voltage.
Meaning
Operating Manual LP 33 Series 50 & 60 kVA
Page 23/57