Code
Message
Q1
4602
OPEN
Q1
4603
CLOSED
BATTERY TEST
4699
IMPOSSIBLE
REMOTE CONTROL
4763
ON
REMOTE CONTROL
4764
OFF
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
The auxiliary contact indicates that the output switch Q1 has
been opened.
The auxiliary contact indicates that the output switch Q1 has
been closed.
Not possible to start battery test (it is postponed) for:
• No mains rectifier or bypass;
• Battery not fully charged;
• Load is below 10% or above 80%.
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.
Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value of
respective parameter (password required):
0 = Only local panel.
1 = Only serial port on CI (TLC).
2 = Both.
Meaning
Operating Manual LP 33 Series 50 & 60 kVA
Page 28/57