Lcd Screen; Metering Screens (Metering) - GE Digital Energy LP 33 Series Operating Manual

50 & 60 kva
Hide thumbs Also See for Digital Energy LP 33 Series:
Table of Contents

Advertisement

6

LCD SCREEN

Shows the UPS system data, events messages and UPS setting.
The data is displayed on 4 rows, 20 characters each, allowing the operator to select between 7
languages: English, German, French, Spanish, Italian, Finnish and Polish.
If there is no keypad activity during 1 minute the LCD screen will return to default screen.
6.1

METERING SCREENS (Metering)

This menu allows, when the keypad Metering is pressed, to show on the LCD panel a series of screens
containing metering information about AC and DC parameters.
LP 33
60kVA P1
APPLICATION ON UPS
= xx%
SERVICE REQUIRED
4.
The signalling, combined with the green LED Operation blinking, is done only in case the respective
parameter (protected by password) has been enabled. See Section 8.4.
Udcp=215V Udcn=215V
Ubp=164V Ubn=164V O
Charge Level
= 100%
Autonomy
= 15min
Beside the indication of the Battery voltage on the display, a letter shows, according to the table
below, the operational status of SBM:
Sigle
Status of charger
O
OFF
T
ON
F
ON
L
ON
B
ON
E
ON
Access to the Parameters for setting the SBM mode is password protected.
Please call your Service Center.
3.
Battery charge level.
4.
Estimated battery backup time with actual load.
Modifications reserved
OPM_LPS_3UO_50K_60K_0US_V010.doc
1. UPS family, nominal rating and for RPA: P + No. UPS.
2. Load status: application on UPS, on utility, supply off, manual
bypass (appl. on manual dev.) and ECO Mode.
3. The load amount as a percentage of the nominal load (referred
to the most loaded phase).
1. Booster DC voltage + pole (Udcp) and – pole (Udcn).
2. Battery DC voltage + pole (Ubp), – pole (Ubn) and the status
SBM (Superior Battery Management).
The functionality of SBM can help to reduce the Battery
recharging time, and improve the lifetime of the Battery.
Charter voltage
0 VDC
Boost (176 VDC)
Floating (164 VDC)
Floating (164 VDC)
Boost (176 VDC)
Boost (179 VDC)
Description
Battery open circuit voltage
Boost charge with new Battery
Battery charged
Normal charge
Boost charge
Battery equalization
Operating Manual LP 33 Series 50 & 60 kVA
Page 21/57

Advertisement

Table of Contents
loading

Table of Contents