Electrical Service Guide - Miller Syncrowave 351 Owner's Manual

Arc welding power source
Table of Contents

Advertisement

3-9. Electrical Service Guide

NOTE
60 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In
Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC)
NOTE
50 Hertz Models
Input Voltage
Input Amperes At Rated Output
Max Recommended Standard Fuse Or Circuit
Breaker Rating In Amperes
Min Input Conductor Size In AWG/Kcmil
Max Recommended Input Conductor Length In
Feet (Meters)
Min Grounding Conductor Size In AWG/Kcmil
Reference: 1996 National Electrical Code (NEC)
OM-354 Page 16
All values calculated at 60% duty cycle.
200
130
200
2
150
(46)
6
All values calculated at 60% duty cycle.
220
138
200
3
125
(38)
6
Without Power
Factor Correction
230
460
575
112
57
46
175
80
70
3
8
8
168
262
409
(51)
(80)
(25)
6
8
8
Without Power
Factor Correction
380
415
80
73
125
110
6
8
214
170
(65)
(52)
6
8
With Power
Factor Correction
200
230
460
112
84
45
150
125
70
4
4
8
117
154
273
(36)
(47)
(83)
6
6
8
With Power
Factor Correction
220
380
415
88
51
47
150
80
70
4
8
141
187
222
(43)
(57)
(68)
6
8
575
34
50
10
287
(87)
10
S-0092-J
8
8
S-0092-J