Instructions:
These instructions inform users of cc3310 systems of the processor installation and
replacement /transfer procedures.

IMPORTANT NOTE:

The systems Sensor Data Records (SDR) must be reprogrammed every time
the hardware configuration changes (any changes to memory, processors, power supplies, power cage, hot
swap back plane, controller boards, or any hardware devices or Field Replaceable Units). Failure to
reprogram the SDR may allow critical system failures to occur without an appropriate Telco alarm.
Use the following procedure to re-write the SDR once the configuration change has been installed:
1. Boot the system using the "cc3310 Diagnostic and Utilities Resource CD".
2. Once the CD has booted, select "Load Configuration Wizard".
3. When the Wizard on the Resource CD begins, Press continue.
4. Select "Server Configuration Wizard" and Continue.
4. Select "run wizard" and continue.
5. Select only the "Load SDR's only on to this server" and continue.
6. Set the "date and time" and continue.
7. Select "update just the SDR repository" and continue.
8. Select "Yes - Activate BMC TAM" and continue.
9. Choose any LED configuration you want and continue.
10. Save the server configuration to disk if you desire and continue.
11. Press "OK to program the SDRs". The server will reboot when the SDR repository is reprogrammed.

Installing Processors

1. Raise the locking bar on the socket.
Figure A
Raising the Locking Bar