Wiring Inspection; Table 1 Power Wiring Terminals - Factory Supplied; Table 2 Torque Specifications - Liebert 600T Series Installation Manual

Multi-module three phase 500 kva to 750 kva, 60 hz
Hide thumbs Also See for 600T Series:
Table of Contents

Advertisement

10.0 W
I
IRING
NSPECTION
1. Verify all power connections are tight.
2. Verify all control wire terminations are tight.
3. Verify all power wires and connections have proper spacing between exposed surfaces, phase-
to-phase and phase-to-ground.
4. Verify that all control wires are run in individual, separate, steel conduit.
Table 1
Power Wiring Terminals - Factory Supplied
UPS Module Rating
500 kVA, 6-Pulse Rectifier
500 kVA, 12-Pulse
Rectifier
625-750 kVA, standard
models with standard input
750 kVA/675 kW and other
modules with optional
input busbar kit
Use 75°C copper wire. Select wire size based on the ampacities in Table 310-16 (see Table 3 of this
manual) and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Connect wire to
the lug using tool and procedure specified by the lug manufacturer.
Table 2
Torque Specifications
Nut and Bolt Combinations
Bolt Shaft Size
1/4
5/16
3/8
1/2
Circuit Breakers With Compression Lugs (For Power Wiring)
Cable Size or Range
#6 - #4
#3 - #1
1/0 - 2/0
3/0 - 200 MCM
250 - 400 MCM
500 - 700 MCM
Terminal Block Compression Lugs (For Control Wiring)
AWG Wire Size or Range
#22 - #14
Use the values in this table unless the equipment is labeled with a
different torque value.
Connection Type
All power connections are top or bottom cable entry to busbars on the right
side of module.
Busbars for DC input, AC output, Neutral and Ground are provided on the
right side of module, with top or bottom cable entry. Rectifier input is top entry
directly to lugs on top of input circuit breaker.
Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input is top entry directly to
lugs on top of input circuit breaker. DC input is top entry to bus bars.
Busbars for AC output, Neutral and Ground are provided on the right side of
module, with top or bottom cable entry. Rectifier input and DC input are top
entry to bus bars.
Grade 2
Standard
Lb-in
53
107
192
428
Lb-in
100
125
150
200
250
300
Lb-in
3.5 to 5.3
Electrical Connections
with Belleville Washers
N-m
Lb-in
6.0
46
12
60
22
95
48
256
N-m
11
14
17
23
28
34
N-m
0.4 to 0.6
N-m
5.2
6.8
11
29

Wiring Inspection