6.15.6 Output Voltage Adjustment

When the MENU key is pressed and held 3-4 seconds during normal 'ac input mode'
of operation, the LCD screen displays the output voltage on the present output
voltage adjust screen:
OUTPUT VOLT. ADJUST
OUTPUT VOLTAGE.=###%
>F1:DATA SET MODE
> ∆/∇ :PREV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
REFERENCE ADJUST: ##
> ∆/∇ :CHANGE DATA
>ENTER: ACCEPT CHANGE
The locations marked ## will show the numerical value of the allowable voltage
adjustment parameter values. Press the 'up' and 'down' arrow keys to adjust the
setting from between –5 to +5. This will cause the unit's output voltage to adjust to
within +/- 2% of its nominal value.
If the inverter is not running, and the output voltage cannot be adjusted; the following
message will be displayed:
Pressing the F1 key will have no effect on this display screen

6.15.7 Charge Mode Select

Press the MENU key to access the menu data screens and press the 'down' arrow
key to scroll to the "Charge Mode Select" adjustment screen display:
CHARGE MODE SELECT
EQUAL CHARGE>OFF ON
>F1:DATA SET MODE
>∆/∇:PRV/NEXT SCREEN
Press the F1 key to display the following active adjustment screen:
CHARGE MODE SELECT
EQUAL CHARGE>OFF ON
>∆/∇:CHANGE DATA
>ENTER:ACCEPT CHANGE
Note: Please consult the factory when utilizing this option. DAMAGE to the systems
battery will occur if this is used improperly.
TOSHIBA
OUTPUT VOLT. ADJUST
OUTPUT VOLT. ADJUST
ADJUSTMENT INHIBITED
> ∆/∇
TO SCROLL
37
Note: ### indicate an actual
numerical value.
Note: Press MENU key to return to
previous menu.