2. Indoor unit failure mode table
NOTE:Blinking patterns of this mode differs from the ones of Troubleshooting check table(9-4.).
Left lamp of
OPERATION
INDICATOR lamp
Not lighted
Room temperature
1-time flash
thermistor
every 0.5-second
2-time flash
Indoor coil thermistor
2.5-second OFF
3-time flash
Serial signal error
2.5-second OFF
11-time flash
Indoor fan motor
2.5-second OFF
12-time flash
Indoor control system
2.5-second OFF
Abnormal point
(Failure mode)
Normal
When the room temperature thermistor
short or open circuit is detected every 8
seconds during operation.
When the indoor coil thermistor short or
open circuit is detected every 8 seconds
during operation.
When the serial signal from the outdoor unit is
not received for a maximum of 6 minutes.
When the rotational frequency feedback
signal is not emitted during 12-second the
indoor fan operation.
When it cannot properly read data in the
nonvolatile memory of the indoor electronic
control P.C. board.
Detection method
13
Check point
Refer to the characteristics of the room
temperature thermistor (9-7.).
Refer to the characteristic of the main
indoor coil thermistor, the sub indoor coil
thermistor (9-7.).
Refer to 9-6.D "How to check miswiring
and serial signal error".
Refer to 9-6.A "Check of indoor fan
motor".
Replace the indoor electronic control
P.C. board.