Mitsubishi Electric MSZ-GA35VA Service Manual page 11

Split-type, heat pump air conditioners
Hide thumbs Also See for MSZ-GA35VA:
Table of Contents

Advertisement

3. Troubleshooting procedure
1) First, check if the OPERATION INDICATOR lamp on the indoor unit is flashing on and off to indicate an abnormality.
To make sure, check how many times the abnormality indication is flashing on and off before starting service work.
2) Before servicing check that the connector and terminal are connected properly.
3) If the electronic control P.C. board is supposed to be defective, check the copper foil pattern for disconnection and the
components for bursting and discoloration.
4) When troubleshooting, refer to 9-2., 9-3. and 9-4.
4. How to replace batteries
Weak batteries may cause the remote controller malfunction.
In this case, replace the batteries to operate the remote controller normally.
1 Remove the front lid and insert batteries.
Then reattach the front lid.
Insert the negative pole of the
batteries first. Check if the polarity
of the batteries are correct.
NOTE : 1. If RESET button is not pressed, the remote controller may not operate correctly.
2. This remote controller has a circuit to automatically reset the microcomputer when batteries are replaced.
This function is equipped to prevent the microcomputer from malfunctioning due to the voltage drop caused by
the battery replacement.
5. How to install the horizontal vane
If horizontal vane is not installed correctly, all of the operation indicator lamps will blink.
In this case, install the horizontal vane correctly by following the procedures 1 to 2.
NOTE: Before installation of the horizontal vane, turn OFF the power supply.
Left
Insert this end first.
INFORMATION FOR MULTI SYSTEM AIR CONDITIONER
OUTDOOR UNIT : MXZ series
Multi system air conditioner can connect two or more indoor units with one outdoor unit.
•Unit won't operate in case the total capacity of indoor units exceeds the capacity of outdoor units. Do not
connect indoor units beyond the outdoor unit capacity.
Operation indicator lamp flashes as shown in the figure below.
•When you try to operate two or more indoor units with one outdoor unit simultaneously, one for the cooling and
the other for heating, the operation mode of the indoor unit that operates earlier is selected. The other indoor
units will start the operation later cannot operate, indicating as shown in the figure below. In this case, please
set all the indoor units to the same operation mode.
•When indoor units starts the operation while the defrosting of outdoor unit is being done, it takes a few minutes
(max. 10 minutes) to blow out the warm air.
•In the heating operation, though indoor unit that does not operate may get warm or the sound of refrigerant
flowing may be heard, they are not malfunction. The reason is that the refrigerant continuously flows into it.
1
OPERATION INDICATOR
11
2 Press RESET button with tip end of ball point pen
or the like, and then use the remote controller.
RESET button
2
Stopper
In procedure
stoppers until they click
into place.
Lock.
Lighted
Blinking
Not lighted
2 2 lock the

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Msz-ga25vaMsz-ga22vaMsz-ga25vaMsz-ga22va