Fluke 1630 Technical Data page 3

Fluke 1630 earth ground clamp meter datasheet
Hide thumbs Also See for 1630:

Advertisement

Ground Loop Resistance (Autorange)
Operating temperature: 0 °C to 50 °C (14 °F to 122 °F)
Range
0.025 - 0.250 Ω
0.250 - 9.999 Ω
10.00 - 99.99 Ω
100.0 - 199.9 Ω
200.0 - 400.0 Ω
400.0 - 600.0 Ω
600.0 - 1500 Ω
1
Note: Loop resistance with no inductance, external magnetic  
field < 50 A/m, external electrical field < 1 V/m, conductor centered. 
Continuity
Beep if resistance < approx. 40 
Ground/leakage current mA~
(Autorange, 50/60 Hz, true-rms, crest factor < 3.0)
Operating temperature: -10 °C to 50 °C (14 °F to 122 °F)
Range
0.200 - 1.000 mA
1.00 - 10.00 mA
10.0 - 100.0 mA
100 - 1000 mA
Current A~
(Autorange, 50/60 Hz, true-rms, crest factor < 3.0 )
Operating temperature: -10 °C to 50 °C (14 °F to 122 °F)
Range
0.20 - 15.00 A
15.00 - 30.00 A
HI/LO Limit Evaluation
Values from 0 
 to 1510 
 may be preset for automatic comparison. If the 
Ω
Ω
measured value is outside of the limit an audible and visual signal is given.
Recording
Measured values can be saved or logged with a defined time interval from 
1 to 255 s. Recorded values may then be recalled on the display of the 
instrument.
3  Fluke Corporation     Fluke 1630 Earth Ground Clamp Meter
Resolution
Operating error
0.002 Ω
± 1.5 % rdg ± 0.05 Ω
0.02 Ω
± 1.5 % rdg ± 0.1 Ω
0.04 Ω
± 2.0 % rdg ± 0.3 Ω
0.4 Ω
± 3.0 % rdg ± 1.0 Ω
2 Ω
± 5.0 % rdg ± 5 Ω
5 Ω
± 10 % rdg ± 10 Ω
20 Ω
± 20 %
Ω
Resolution
Operating error
0.001 mA
± 2.5 % rdg ± 0.05 mA
0.01 mA
± 2.5 % rdg ± 0.05 mA
0.1 mA
± 2.0 % rdg ± 0.3 mA
1 mA
± 2.0 % rdg ± 3 mA
Resolution
Operating error
0.01 A
± 2.0 % rdg ± 0.03 A
0.01 A
± 3.0 % rdg ± 0.03 A
The Fluke 1630 Earth Ground Clamp
Meter includes:
Carrying case with strap
1
Resistance test loop
Users manual in English, French,
Spanish, German, Italian, Portuguese
and Simplified Chinese
Fluke. Keeping your world
up and running.™