Download Print this page

Carrier 33CS2PPRH-02 Owner's Manual page 5

Commercial thermostat

Advertisement

and up to three reset reminders (as enabled by the install-
er). One of the reminders will flash. The display will
show the percentage of time used by that reminder item.
3. Repeatedly press the SET button until the reminder to be
cleared flashes.
4. Press and hold the DONE button for about 3 seconds to
remove the reminder. The percentage associated with the
reminder will be reset to zero.
5. Press the DONE button again.
6. Close the thermostat door.
FAHRENHEIT OR CELSIUS DISPLAY — The thermostat
is preset to display the temperature in degrees Fahrenheit. The
user can change the display to Celsius if desired. To change the
display, perform the following:
1. Open the thermostat door.
2. Press and hold the buttons underneath the heat and cool
set points simultaneously. The screen will display "01."
3. Press the UP arrow button until 01 changes to 02. The F
(Fahrenheit) will also be displayed.
4. Press the soft key under the F icon until C (Celsius) ap-
pears.
5. Press the DONE button.
6. Close the thermostat door.
BACKLIGHTING — The thermostat may feature a low level
amount of backlighting until a button is pressed, which increas-
es the lighting temporarily. The user can adjust the intensity of
the backlighting or turn it off completely. The range is off (OF),
and 1 to 5 levels of brightness. To change the backlighting lev-
el, perform the following:
1. Open the thermostat door.
2. Press and hold the buttons underneath the heat and cool
set points simultaneously. The screen will display "01."
3. Press the UP arrow button until 01 changes to 03. The
number 3 (the default backlight setting) will be displayed
next to it.
4. To increase the backlight level, press the rightmost soft
key and then press the UP arrow button. To decrease the
backlight level, press the rightmost lower button and then
press the DOWN arrow button. Change the setting to OF
by pressing the DOWN arrow button to completely re-
move backlighting.
5. Press the DONE button.
6. Close the thermostat door.
PROGRAMMABLE / NON-PROGRAMMABLE SET-
TING — It is possible to convert the thermostat operation
from programmable to non-programmable. This eliminates the
advanced features. When switching to the non-programmable
format, the programming, hold, holiday and Smart Recovery
features are lost. Switching to non-programmable operation
also means that some of the thermostat's energy saving features
are lost. The time of day and day of the week will still show on
the display and the user will still be able to increase or decrease
the temperature settings manually.
To switch thermostat operation, perform the following:
1. Open the thermostat door.
2. Press and hold the buttons underneath the heat and cool
set points simultaneously. The screen will display "01"
and up to three reset reminders.
3. Press the UP arrow button until 01 changes to 05. The P
icon (the default setting) will be displayed next to it.
4. Press the rightmost soft key and then press the UP arrow
button until the desired operation is shown. P stands for
programmable and nP stands for non-programmable.
5. Press the DONE button.
6. Close the thermostat door.
NUMBER OF PROGRAMMING PERIODS — The
mostat is preset with four programmable time periods. This can
be changed to two. To change the number of time periods, per-
form the following procedure:
1. Open the thermostat door.
2. Press and hold the buttons underneath the heat and cool
set points simultaneously. The screen will display "01"
and up to three reset reminders.
3. Press the UP arrow button until 01 changes to 06. The
number 4 (the default setting) will be displayed next to it.
4. Press the rightmost soft key and then press the UP arrow
button until the desired number of time periods is shown.
5. Press the DONE button.
6. Close the thermostat door.
DAYLIGHT SAVINGS TIME — The thermostat will auto-
matically change the clock according to daylight savings time
procedures twice a year. Some areas do not use daylight sav-
ings time. To turn off the daylight savings time feature, perform
the following procedure:
1. Open the thermostat door.
2. Press and hold the buttons underneath the heat and cool
set points simultaneously. The screen will display "01"
and up to three reset reminders.
3. Press the UP arrow button until 01 changes to 08. The
ON icon (the default setting) will be displayed next to it.
4. Press the rightmost soft key and then press the UP arrow
button until the desired number setting (OF) is shown.
5. Press the DONE button.
6. Close the thermostat door.
Service Reminders —
when it is time to change the UV light, change the filter, or per-
form scheduled maintenance. Each reminder will be displayed
on the upper left of the screen. For important safety reasons, do
not change a UV light; ask your dealer to replace the UV light.
To remove the reminder after the service has been performed,
press and hold the DONE button for about 3 seconds.
Outdoor Temperature Display —
automatically displays the outdoor temperature when the ther-
mostat door is closed if a valid sensor has been wired to the
thermostat.
Auto Changeover —
five modes: heat, cool, Em heat (heat pump version only), heat
cool (auto mode) and off. When the mode selection is auto
mode, the system is allowed to switch from heating to cooling
or from cooling to heating to maintain the temperature set
points.
Smart Recovery —
tions the space from one temperature period (occ, occ2, occ3,
unocc) to the next so that the space temperature matches the
temperature set point at the start of each time period. This
means, for example, that if the unocc period temperature set-
ting is lower than the period that precedes it, then the thermo-
stat will start cooling down the space before the beginning of
the scheduled unocc period. The thermostat does this at an en-
ergy efficient rate. This not only helps make the space as com-
fortable as possible, it also makes thermostat usage more cost
effective.
Power Outage —
thermostat will not need to be reprogrammed. The settings are
retained in memory.