Unit Start-Up Procedure - Heat Controller H 006 Installation, Operation And Maintenance Manual

Hc series 1/2 to 5 tons commercial water source heat pumps
Table of Contents

Advertisement

5. Two factors determine the operating limits of Heat
Controller heat pumps, (a) return air temperature,
and (b) water temperature. When any one of these
factors is at a minimum or maximum level, the other
factor must be at normal level to insure proper unit
operation.
a. Adjust the unit thermostat to the warmest setting.
Place the thermostat mode switch in the "COOL"
position. Slowly reduce thermostat setting until the
compressor activates.
b. Check for cool air delivery at the unit grille within a
few minutes after the unit has begun to operate.
Note: Units have a five minute time delay in the
control circuit that can be eliminated on the CXM
control board as shown below in Figure 7. See
controls description for details.
c. Verify that the compressor is on and that the water
flow rate is correct by measuring pressure drop
through the heat exchanger using the P/T plugs
and comparing to tables 8a through 8e.
d. Check the elevation and cleanliness of the
condensate lines. Dripping may be a sign of a
blocked line. Check that the condensate trap is
filled to provide a water seal.
e. Refer to table . Check the temperature of both
entering and leaving water. If temperature is within
range, proceed with the test. If temperature is
outside of the operating range, check refrigerant
pressures and compare to table1. Verify correct
water flow by comparing unit pressure drop
across the heat exchanger versus the data in
tables 8a through 8e. Heat of rejection (HR) can
be calculated and compared to submittal data
capacity pages. The formula for HR for systems
with water is as follows:
HR = TD x GPM x 500, where TD is the
temperature difference between the entering and
leaving water, and GPM is the flow rate in U.S.
GPM, determined by comparing the pressure drop
across the heat exchanger to table 8.
f.
Check air temperature drop across the air coil when
compressor is operating. Air temperature drop
should be between 15°F and 5°F [8°C and 14°C].
g. Turn thermostat to "OFF" position. A hissing noise
indicates proper functioning of the reversing valve.
6. Allow five (5) minutes between tests for pressure to
equalize before beginning heating test.
a. Adjust the thermostat to the lowest setting. Place
the thermostat mode switch in the "HEAT" position.
b. Slowly raise the thermostat to a higher
temperature until the compressor activates.
c. Check for warm air delivery within a few minutes
after the unit has begun to operate.
d. Refer to table . Check the temperature of both
entering and leaving water. If temperature is within
range, proceed with the test. If temperature is
outside of the operating range, check refrigerant
pressures and compare to table 1. Verify correct
6

UNIT START-UP PROCEDURE

7. If unit fails to operate, perform troubleshooting
8. When testing is complete, set system to maintain
. BE CERTAIN TO FILL OUT AND FORWARD ALL
Note: If performance during any mode appears abnormal,
refer to the CXM section or troubleshooting section of
this manual. To obtain maximum performance, the air
coil should be cleaned before start-up. A 10% solution of
dishwasher detergent and water is recommended.
WARNING! When the disconnect switch is
closed, high voltage is present in some areas
of the electrical panel. Exercise caution when
working with energized equipment.
CAUTION! Verify that ALL water control
valves are open and allow water flow prior
to engaging the compressor. Freezing of the
coax or water lines can permanently damage
the heat pump.
Figure 27: Test Mode Pins
water flow by comparing unit pressure drop across
the heat exchanger versus the data in table 8.
Heat of extraction (HE) can be calculated and
compared to submittal data capacity pages. The
formula for HE for systems with water is as follows:
HE = TD x GPM x 500, where TD is the
temperature difference between the entering and
leaving water, and GPM is the flow rate in U.S.
GPM, determined by comparing the pressure drop
across the heat exchanger to table 8.
e. Check air temperature rise across the air coil when
compressor is operating. Air temperature rise should
be between 0°F and 0°F [11°C and 17°C].
f.
Check for vibration, noise, and water leaks.
analysis (see troubleshooting section). If the check
described fails to reveal the problem and the unit
still does not operate, contact a trained service
technician to insure proper diagnosis and repair of
the equipment.
desired comfort level.
WARRANTY REGISTRATION PAPERS TO HEAT
CONTROLLER.
� WARNING! �
� CAUTION! �
Short test pins
together to enter Test
Mode and speed-up
timing and delays for
0 minutes.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents