Honeywell HCM-631N - Quietcare 3 Gallon Owner's Manual page 23

User guide
Table of Contents

Advertisement

2 IN. PER FT
10 FT MAX
2 IN. PER FT
SUPPORTED REMOTE HOSE
NOTES:
• Slope hose up in direction of steam flow at 2 in. per foot;
• Slope hose down in direction of steam flow at 3/4 in. per foot;
• Maximum length of remote steam hose is 20 ft.
• Height of P-traps must be greater than the duct static pressure. (Typical 3 in.
will suffice.)
• Minimize sharp bends and elbows.
• Insulating the remote hose in unconditioned spaces will sustain efficiency better
than not insulating the hose.
NO SLOPE
KINKED
TrueSTEAM Humidification System 69-2285—01
20 FT MAX
WITH TRAP
P - TRAP
20 FT MAX
GENTLE BEND
2 IN. PER FT
OBSTRUCTION
DRAIN
SAG
5 FT MAX
IF NO SLOPE
IF NO SLOPE
DRAIN
TYPICAL INSTALLATION
WHEN TrueSTEAM IS ABOVE
REMOTE NOZZLE
P - TRAP
NOTE: HEIGHT OF TRAP MUST BE GREATER
THAN THE DUCT STATIC PRESSURE
NO SLOPE
2 IN. PER FT
DRAIN
DRAIN
P - TRAP
P - TRAP
M24915
UNDRAINED
ELBOW
M24915
21

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Truesteam

Table of Contents