Panasonic FP Web-Server User Manual page 89

Fp series programmable controller, hardware / configuration
Hide thumbs Also See for FP Web-Server:
Table of Contents

Advertisement

Http Server Functions/ Web Pages
Display on the HTML editor (Netscape Composer):
Display on the browser (Netscape Browser):
The setup of the field for PLC data display always has the format {TTxxxy_aa_bb} with the
following parameters:
TT
PLC Data Type. Implemented PLC data identifiers: DT, FL, LD, R, X, Y
xxxy
Address of the PLC Data, e.g. DT200 or Y7.
The address range supported by the FP Web-Server is 0 ... 32765.
For internal relays, the last position of the address is a hexadecimal number from 0...F, e.g. R2F
aa
Numbers: Number of characters reserved in HTML. The rest will be cut off.
Internal Relays: Text that should be displayed at internal relay state 0, e.g. OFF .
bb
Numbers: Number format, i.e. type of the display. See below.
Internal Relays: Text that should be displayed at internal relay state 1, e.g. ON .
The data type and address part TTxxxy can be replaced by the corresponding variable name
(see page 82) from the FPWIN Pro project, e.g. {'VarName'_aa_bb} or {'name'_5_i}.
There is no space allowed between the curly bracket and the first character. For example {
DT3_4_u} or { 'name'_5_i} is not allowed. It will be interpreted as a Java Script (see page 95)
command and copied unchanged into the final HTML file.
The setup of the format specification bb for numbers is [flags][width][.precision][l]type
Only the specification 'type' is obligatory. The other inputs are optional. In the following list the
corresponding FPWIN Pro types are listed in brackets: