Toshiba V200 Series User Manual page 92

V200 series programmable logic controllers
Table of Contents

Advertisement

Channel Type Selection Values Table:
Use the following values in the Input and output channel type select register to configure the corresponding channel
to particular type.
e.g. If you want to configure the Input channel 3 of GAD208**S model as ( 0 – 10 V ) type, then move value 19 in
MWxx16 configuration register. Here xx digital denotes the slot number in which the GAD208**S model is
connected to PLC. The Conversion Enable Flag should be one to start the conversion (A to D or D to A).
Input Channel Type
Not Defined
mV( 0 - 100 mV )
mV( 0 - 50 mV )
mA( 0 - 20mA )
mA( 4 - 20mA )
Voltage ( 0 - 10V )
Voltage ( 1 - 5V )
RTD PT-100 (alpha1)
RTD PT-100 (alpha2)
RTD PT-1000
Thermocouple (B-Type) 11
Thermocouple (R-Type) 12
Thermocouple (S-Type) 13
Thermocouple (E-Type) 14
Thermocouple (J-Type) 15
Thermocouple (K-Type) 16
Thermocouple (N-Type) 17
Thermocouple (T-Type)
Output Channel Type
Not Defined
mA( 4 - 20mA )
Voltage ( 0 - 10V )
Value
0
1
3
5
7
19
20
9
10
21
18
Value
0
1
2
Page 84