8.1.5
Test programs
Special functions can be triggered in the appliances by
activating various test programs. These programs are
given in detail in the following table 8.4.
• The test programs P.0 to P.6 are started when "Power
ON" is turned on and the "+" key is pressed for 5 s.
The display shows "P.1".
• Press the "+" key to start counting the test number
upwards.
• By pressing the "i" key the appliance is now put unto
operation and the test program started.
• Press "i" and "+" simultaneously to end the test pro-
grams. You can also end the test programs by not
pressing any key for 15 minutes.
Display
Meaning
P. 0
Venting test program
1x "i" key: start bleeding the heating pump
(display: HP)
2x "i" key: start bleeding the charging pump
(display: LP)
3x "i" key: end bleeding program
Note: the bleeding program runs for approx. 6.5 mins.
P. 1
Test program whereby the appliance is operated at full
load after successful ignition
P. 2
Test program whereby the appliance is operated with
minimum gas volume after successful ignition
P. 5
Test program for safety thermostat test; appliance
heats up by bypassing a control shutdown until the
safety thermostat shutdown temperature of 97 °C is
reached
Table 8.4 Test programs