ARENA / RANGER
EN2Z-0906GE51 R0708
2. To change a value, click on the value in the Value/Unit column. In the Value
dialog box, enter new value in the New Value field. Click Apply button, then
click OK button.
3. To enter an alias name for a property name, click the Configure icon
end of the row. In the Configure dialog box, enter the alias name in the Alias
field. Click OK.
NOTE:
It is forbidden to use the slash character "/" in alias names because
this may result in an unexpected behavior of ARENA.
4. To print a datapoint properties list, check all properties (Multi-selection using
CTRL key is possible), you want to add to the printed list.
5. Click Print.
The list is built up in a new dialog.
6. Click Print.
7. In the Print dialog box, select the printer and desired options and click Print.
1. In the Value/Unit column, click the value of the datapoint you want to override.
2. In the Value dialog box, enter the new value in the New Value field.
3. Click Apply.
4. Click OK.
The datapoint value is updated as displayed in the list. If the Manual column is
available, the datapoint is checked as Manual (overridden).
NOTE: Online changes will be stored in the controller RAM only.
This function allows getting an overview of any datapoints that are currently in
manual mode.
1. If not already done, display the Manual column in the datapoints list. To
configure the list display, please refer to "List Display Configuration" in the
"Basic Functions" section.
70

Override Datapoint Value

Show Datapoints in Manual Override

USER GUIDE