Downward Venting - Trane UC SERIES Installer's Manual

Upflow / horizontal and downflow / horizontal gas-fired condensing furnaces
Table of Contents

Advertisement

HORIZONTAL AND VERTICAL VENTING
r
SUPPORT HORIZONTAL PIPE EVERY 3' 0" WITH
THE FIRST SUPPORT AS CLOSE TO THE
FURNACE AS POSSIBLE. INDUCED DRAFT
BLOWER, HOUSING, AND FURNACE MUST NOT
SUPPORT THE WEIGHT OF THE FLUE PIPE.
t

DOWNWARD VENTING

Furnace may be in vertical or
horizontal configuration.
All horizontal pipes must be supported
at a maximum of 3 foot intervals
Slope 1/4" per ft.
NOTES:
A) CONDENSATE TRAP FOR VENT PIPE MUST BE A MINIMUM OF
6 INCHES IN HEIGHT.
B) CONDENSATE TRAP FOR VENT AND INLET PIPE MUST BE CONNECTED INTO A CONDENSATE DRAIN PUMP; AN OPEN OR
VENTED DRAIN; OR IT CAN BE CONNECTED TO THE OUTLET HOSE OF THE FURNACE'S CONDENSATE TRAP. OUTDOOR
DRAINING OF THE FURNACE AND COIL CONDENSATE IS PERMISSIBLE IF ALLOWED BY LOCAL CODES. CAUTION SHOULD
BE TAKEN TO PREVENT DRAINS FROM FREEZING OR CAUSING SLIPPERY CONDITIONS THAT COULD LEAD TO PERSONAL
INJURY. EXCESSIVE DRAINING OF CONDENSATE MAY CAUSE SATURATED GROUND CONDITIONS THAT MAY RESULT IN
DAMAGE TO PLANTS.
C) THE CONDENSATE TRAP SHOULD BE PRIMED AT INITIAL START UP PRIOR TO HEATING SEASON OPERATION.
18-CD19D5-10
Installer's Guide
When the vent pipe is exposed to
temperatures below freezing, i.e.,
when it passes through unheated
spaces, etc., the pipe must be
insulated with 1/2 inch (22.7 mm)
thick Armaflex-type insulation or
equal. If the space is heated
sufficiently to prevent freezing,
then the insulation would not be
required. If domestic water pipes
are not protected from freezing,
then it is assumed the space
meets the condition of a heated
space.
40 Inch
Upflow or
Downflow
Furnace
6" Min.
CAUTION
!
13

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents