Trane RTHD Troubleshooting Manual page 32

Air and water cooled chillers
Table of Contents

Advertisement

32
Over/Under Voltage
Table 6.
Starter Module Input-to-Line Voltage Conversion
Starter Module Input Voltage
J5-1,2
J5-3,4
J5-5,6
(Volt AC)
14.4
14.9
15.4
15.9
16.3
16.8
17.3
17.8
18.3
18.8
19.3
19.8
20.3
20.8
21.3
21.8
22.3
22.8
23.3
23.8
24.3
24.8
25.3
25.7
26.2
26.7
27.2
27.7
28.2
Acceptable tolerance between actual incoming line-to-line voltage and displayed
voltage (on DynaView or TechView) is +\- 3% of reading. The accuracy of the
meter being used to measure the actual line-to-line voltage needs to be added to
this tolerance.
Acceptable tolerance between the Starter module input voltage measurements
listed
Table 6
with respect to the displayed line-to line voltage (on DynaView or
TechView) is +\- 3% of reading.
Incoming Line-to-Line Voltage
(Volt AC)
290
300
310
320
330
340
350
360
370
380
390
400
410
420
430
440
450
460
470
480
490
500
510
520
530
540
550
560
570
RLC-SVD05A-EN