Trane TTA240F Series Installation Operation & Maintenance page 12

Tta240f/tta200fd series split system cooling condensers 20-ton
Hide thumbs Also See for TTA240F Series:
Table of Contents

Advertisement

.
Figure 6.
Typical Field Wiring - ReliaTel Control
TTA240F/TWE240E
Field Wiring:
A
3 power wires, line voltage
B
3 power wires, line voltage for 3
phase; 2 wires for single phase
C
Cooling only thermostat: 5 wires,
24 volts***
One stage electric heat: add 1
additional wire, 24 volts
Two stage electric heat: add 2
additional wires, 24 volts
D
Add 4 wires, 24 volts
One stage electric heat: add 1
additional wire, 24 volts
Two stage electric heat: add 2
additional wires, 24 volts
E
Zone Sensor: 2 wires minimum or
10 wires maximum, 24 volts***
(# of wires are dependent upon
zone sensor selection)
F
NSB Panel: 8 wires, 24 volts***
12
Installation
Note: 1) Wiring shown with dashed
lines is to be furnished
and installed by the
customer. All customer
supplied wiring must be
copper only and must
conform to NEC and local
electrical codes. Codes
may require line of sight
between disconnect
switch and unit.
2) When electric heater
accessory is used, single
point or dual point power
entry is optional, since
single point power option
is through electric heater
only.
3) ***Note: Choose only 1 of
the following:
thermostat
zone sensor
night setback panel
TTA-SVN03A-EN