Table Pd-6 - Belt Drive Evaporator Fan Performance - Ysc060Ad*L - Low Heat - Downflow Configuration - (Si); Table Pd-6A - Belt Drive Evaporator Fan Performance - Ysc060Ad*L - Low Heat - Downflow Configuration - (Ip) - Trane Precedent YSC060-120 User Manual

Packaged gas/electric rooftop units 50hz
Table of Contents

Advertisement

Table PD-6 - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (SI)

25
50
m3/h
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Low Static Drive
2720
716
0.28
768
0.32
3060
791
0.38
840
0.43
3400
867
0.51
914
0.56
3740
944
0.66
989
0.73
4080
1022
0.85
1064
0.92
External Static Pressure (Pascals)
275
300
m3/h
RPM
kW
RPM
kW
1.12 Nom kW Standard Motor & Drive
2720
1135
0.75
1166
0.80
3060
1188
0.90
1218
0.96
3400
1244
1.08
1273
1.14
3740
1300
1.27
-
4080
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1.12 kW - Fan Motor Heat (kW) = 1.144 x Fan kW + 0.132

Table PD-6a - Belt Drive Evaporator Fan Performance - YSC060AD*L - Low Heat - Downflow Configuration - (IP)

0.10
0.20
CFM
RPM
BHP
RPM
BHP
1600
716
0.37
768
0.43
1800
791
0.51
840
0.57
2000
867
0.68
914
0.76
2200
944
0.89
989
0.97
2400
1022
1.14
1064
1.23
External Static Pressure (Inches of Water)
1.10
1.20
CFM
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Drive
1600
1135
1.01
1166
1.07
1800
1188
1.21
1218
1.28
2000
1244
1.45
1273
1.53
2200
1300
1.70
-
2400
-
-
-
Notes:
Data Includes Pressure Drop Due To Wet Coils And Filters.
1 1/2 HP - Fan Motor Heat (MBH) = 2.915 x Fan BHP + 0.451
RT-PRC017-EN
Performance
Data
External Static Pressure (Pascals)
75
100
RPM
kW
RPM
kW
816
0.36
863
0.39
884
0.47
927
0.51
955
0.61
994
0.66
1027
0.78
1063
0.84
1101
0.98
1135
1.04
325
350
RPM
kW
RPM
kW
1198
0.85
1228
0.91
1249
1.01
1279
1.07
1303
1.20
1332
1.27
-
-
-
-
-
-
-
-
-
-
External Static Pressure (Inches of Water)
0.30
0.40
RPM
BHP
RPM
BHP
1-1/2 HP Standard Motor & Low Static Drive
816
0.48
863
0.53
884
0.63
927
0.69
955
0.82
994
0.89
1027
1.05
1063
1.12
1101
1.32
1135
1.40
1.30
1.40
RPM
BHP
RPM
BHP
1198
1.14
1228
1.22
1249
1.36
1279
1.44
1303
1.61
1332
1.70
-
-
-
-
-
-
-
-
-
-
125
150
RPM
kW
RPM
kW
RPM
909
0.44
953
0.50
993
969
0.56
1010
0.61
1049
1033
0.71
1070
0.76
1107
1099
0.89
1134
0.94
1168
1168
1.10
1200
1.16
1233
375
RPM
kW
1258
0.96
1307
1.13
-
-
-
-
-
-
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
0.50
0.60
RPM
BHP
RPM
BHP
RPM
909
0.60
953
0.67
993
969
0.75
1010
0.82
1049
1033
0.95
1070
1.02
1107
1099
1.19
1134
1.26
1168
1168
1.48
1200
1.55
1233
1.50
RPM
BHP
1258
1.29
1307
1.51
-
-
-
-
-
-
Factory Supplied Motors, In Commercial Equipment, Are
Definite Purpose Motors, Specifically Designed And
Tested To Operate Reliably And Continuously At All
Cataloged Conditions. Using The Full Horsepower Range
Of Our Fan Motors As Shown In Our Tabular Data Will
Not Result In Nuisance Tripping Or Premature Motor
Failure. Our Product's Warranty Will Not Be Affected.
175
200
225
kW
RPM
kW
RPM
kW
1.12 Nom kW Std Mtr & Drive
0.55
1031
0.60
1067 0.65
0.67
1087
0.73
1122 0.79
0.82
1143
0.88
1178 0.95
0.99
1202
1.05
1235 1.12
1.22
-
-
-
0.70
0.80
0.90
BHP
RPM
BHP
RPM BHP
1-1/2 HP Std Motor & Drive
0.74
1031
0.81
1067 0.87
0.90
1087
0.99
1122 1.06
1.10
1143
1.18
1178 1.27
1.33
1202
1.41
1235 1.51
1.63
-
-
-
250
RPM
kW
1101 0.70
1156 0.85
1212 1.02
1267 1.19
-
-
-
1.00
RPM BHP
1101 0.94
1156 1.14
1212 1.36
1267 1.60
-
-
-
19

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents