Led Activity; Red Service Led; Green Status Led; Yellow Comm Led - Trane BCHC Installation & Operation Manual

Blower coil air handler, air terminal devices 400 to 3000 cfm, “ao” and later design sequence
Hide thumbs Also See for BCHC:
Table of Contents

Advertisement

LED Activity

Red Service LED

The red LED normally indicates if the unit
controller is operating properly or not.
Reference Table M-T-1.

Green Status LED

The green LED normally indicates
whether the controller is powered on (24
VAC supplied). Reference Table M-T-2.

Yellow Comm LED

The yellow comm LED blinks at the rate
the controller receives communication.
The yellow LED does not blink when the
controller is transmitting communication
data. Reference Table M-T-3.
Note: If the service push button is held
down for more than 15 seconds, the
Tracer ZN controller will uninstall itself
from the ICS™ communication network
and shut down all unit operation. This
mode is indicated by the red Service LED
flashing once every second. See the Red
Service LED section. Use Rover™
service tool to restore the unit to normal
operation. Refer to the Rover™ product
literature for more information.

Manual Output Test

The purpose of the manual output test
sequence is to verify output and end
device operation. Use the manual output
test to:
• Verify output wiring and operation
without using Rover™, service tool.
• Force the water valve to open and
balance the hydronic system.
Note: The manual output test is not an
automatic cycle. You must press the Test
button to proceed through each step.
The controller observes all diagnostics
that occur during the test sequence.
Although an automatic diagnostic reset
sequence exists as part of the controller's
normal operation, the automatic diagnos-
tic reset feature is not active during the
test sequence.
If left in an individual test step, the
controller remains in test mode for 60
BCXC-SVX01A-EN
Maintenance
Table M-T-1. Red Service LED Activity
LED Activity
Off continuously after
power is applied to the controller.
On continuously, even when
power is first applied to the
LED flashes about once
every sec.
Black Service push button
Table M-T-2. Green Status LED Activity
Green LED activity
On continuously
Blinks (one blink)
Blinks (2 blinks)
LED blinks (1/4 sec.
on, 1/4 sec., off for 10 sec)
LED off
Note 1: The Wink feature allows you to identify a controller. By sending a request from Rover service tool, you can request
the controller to wink (blink on and off as a notification that the controller received the signal). The green LED blinks (1/4
second on, 1/4 second off for 10 seconds) during Wink mode.
Table M-T-3. Yellow Comm LED Activity
LED activity
Off continuously
LED blinks or flickers
LED on continuously
minutes and then exits to normal
operation.
Many service calls are due to unit
diagnostics. The test sequence resets unit
diagnostics and attempts to restore
normal unit operation prior to testing the
outputs. If the diagnostics remain after a
reset, the STATUS LED indicates the
diagnostic condition is still present (two
blinks).
Manual Output Test Procedure
Follow the procedure below to test the
Tracer
ZN010, ZN510, or ZN520
controller.

Troubleshooting

Description
Normal operation
Someone is pressing the Service
button or the controller has failed.
Uninstall (normal controller mode).
Use Rover™ service tool to restore normal unit operation.
Use the Service button to install the Tracer
communication network.
Description
Power on (normal operation)
The controller is in manual output test mode.
No diagnostics present.
The controller is in manual output test mode.
One or more diagnostics are present.
Wink mode (Note 1).
Power is off.
Controller failure
Test button is pressed.
Description
The controller is not detecting any communication.
(Normal for standalone applications.)
The controller detects communication.
(Normal for communicating applications, including data sharing.)
Abnormal condition or extremely high traffic on the link.
high traffic on the link.
1. Press and hold the Test button for at
least two seconds (not exceeding five
seconds), and then release, to start the
test mode.
2. The test sequence will turn off all
outputs and then attempt to clear all
diagnostics.
3. Press the Test button several more
times (no more than once per second)
to advance through the test sequence.
The outputs are not subject to minimum
times during the test sequence. However,
the test sequence only permits one step
per second which limits minimum output
time.
®
ZN520 controller in a
49