9.3.5

Temperature

You activate the monitoring of the module temperature with the parameter entry
/Environment/Extended/Temperature/Monitoring (0.24.01).
You can set the following values:
Alarm
Warning
No monitoring
The current module temperature is shown in the parameter entry
/Environment/Status/Temperature (0.24.02).
9.3.6

Battery

You can switch the battery off for storage with the parameter entry
/Environment/Extended/Battery/Switch Off (0.25.01), and so substantially
lengthen the life of the battery in storage.
After a minimum operating period of 30 minutes after Power Up, SICLOCK
TC100 checks once whether the battery is switched off. If necessary, the battery
is then switched on automatically, and a message is output.
Notice
If the supply voltage is switched off while the battery is switched off, the SICLOCK
TC100 loses the hardware time and the archives.
This command may only be executed by qualified personnel.
See Battery (Chapter 11.1).
Siemens AG 2010 All Rights Reserved
®
SICLOCK
TC100 Operating Instructions
Parameter assignment
9-8