Simatic Mode - Siemens SICLOCK TC100 Operating Instructions Manual

Plant central clock
Table of Contents

Advertisement

9.2.2

SIMATIC mode

SIMATIC mode is supported at the Ethernet port by two protocols:
PCS7-compatible mode
S5-compatible mode
The setting is made with the parameter
/SIMATIC Mode/Ethernet 1 (0.15.01).
Mode
You set the send clock between 0 s, 1 s and 10 s with the parameter entry
/SIMATIC Mode/Ethernet 1/Mode (0.15.01).
Send condition
You define whether the signal is always output or only when synchronized with
the parameter entry /SIMATIC Mode/Ethernet 1/Send Condition (0.15.01).
Destination address
You define the send address of the SIMATIC mode with the parameter entry
/SIMATIC Mode/Ethernet 1/Destination Address (0.15.01). The broadcast
address FF:FF:FF:FF:FF:FF is typically set.
Siemens AG 2010 All Rights Reserved
®
SICLOCK
TC100 Operating Instructions
Parameter assignment
9-7