Venting - Rheem AP15317 Use And Care Manual

Direct vent gas tankless water heater
Table of Contents

Advertisement

The  water  heater  must  be  installed  with  a  3"/5"  diameter  UL  approved  Category  III  Concentric  Stainless  
Steel  appliance  concentric  vent  pipe  or  Rheem  approved  concentric  vent  pipe.
DANGER:  Failure  to  
install  the  appliance  vent  
adapter  and  properly  vent  the  
water  heater  to  the  outdoors  
as  outlined  in  the  Venting  
section  of  this  manual  will  
result  in  unsafe  operation  of  
the  water  heater,  causing  death,  
serious  injury,  explosion,    
or  fire.  To  avoid  the  risk    
of  fire,  explosion,  or  
asphyxiation  from  carbon  
monoxide,  NEVER  operate  the  
water  heater  unless  it  is  
properly  vented  and  has  
adequate  air  supply  for  proper  
operation  as  outlined  in  the  
Venting  section  of  this  manual.
WARNING:  Use  only  3"/5"  
UL  approved  Category  III  
Concentric  Stainless  Steel  vent  
material  or  Rheem  approved  
concentric  vent  material.  No  
other  vent  material  is  
permitted.
WARNING:  Follow  
concentric  vent  
manufacturer's  installation  
instructions  and  their  
recommended  clearances  to  
combustibles.
Number  of  
Maximum  
90°  elbows  
Length  of  
(bends)
Straight  Pipe
1
39'
(12.0  m)
2
37'  6"
(11.5  m)
3
36"
(11.0  m)
4
34'  6"
(10.5  m)
5
33'
(10.0  m)
6
31'6"
(9.5  m)
AP15317 (10_09) DV Gas Manual 10 30 09.indd 9

Venting

The  installation  of  venting  must  comply    
with  national  codes,  local  codes  and  the    
vent  manufacturer's  instructions.
The  water  heater  must  be  vented  to  the  
outdoors  as  described  in  these  instructions.  
DO  NOT  connect  this  water  heater  to  a  
chimney.  It  must  be  vented  separately  from  
all  other  appliances.
All  concentric  vent  components  (adapters,  
pipe,  elbows,  terminals,  etc.)  should  be  
Rheem  approved  Stainless  Steel  Venting  
Material    
(e.g.   A L29-­4C).
The  specified  vent  termination  must  be  used.  
(Refer  to  pages  13  and  14  for  an  example  of  
the  concentric  vent.)
Use  the  screws  provided  to  connect  
the  concentric  vent  pipe  with  the  anti-­
disconnection  joint.
The  unit  can  be  vented  either  horizontally    
or  vertically.
Concentric  vent  pipe  runs  must  be  
adequately  supported  along  both  horizontal  
and  vertical  runs.
The  maximum  recommended  unsupported  
span  should  be  no  more  than  five  (5)  feet  
(1.5  m).  Support  isolation  hanging  bands  
should  be  used.  DO  NOT  use  wire.  (See  
diagram)
Venting  Lengths
MAXIMUM  VENT  LENGTH:  
The  system  will  not  operate  if  there  is  
excessive  restriction  (pressure  drop)  in  the  
venting  system.   A  maximum  39'(12.0  m)  of  
vent  pipe  may  be  used  provided  there  is  only  
one  90°  elbow  in  the  system.  If  additional  
elbows  are  required:  two  elbows  can  be  used  
with  37'  6"(11.5  m),  three  elbows  can  be  used  
with  36'    (11.0  m)  or  four  elbows  can  be  used  
with  34'  6"  (10.5  m)  of  vent  pipe.  (See  table)
A  94°  elbow  is  equivalent  to  1'6"  (.5  m)  of  
straight  pipe.   A  45°  elbow  is  equivalent  to  
9"  (.25  m)  of  straight  pipe.
The  vent  termination  does  not  count  
in  equivalent  to  pipe  calculation  when  
determining  total  vent  lengths.  
The  vent  should  be  installed  with  a  slight  
downward  slope  of  1/4"  per  foot  of  
horizontal  run  toward  the  vent  terminal  (see  
diagram).  This  ensures  that  any  condensate  
formed  during  operation  of  the  unit  is  
evacuated  from  the  appliance  and  to  prevent  
rain  from  entering  the  appliance.
An  upward  slope  toward  the  vent  terminal  is  
not  acceptable  for  horizontal  venting  without  
Notes  on  pre-­existing  vent:
If  the  water  heater  is  being  installed  as  a  
replacement  for  an  existing  water  heater,  a  
thorough  inspection  of  the  existing  venting  
and  air  intake  system  must  be  performed  
prior  to  any  installation  work.  Verify  that  the  
correct  materials,  vent  lengths  and  terminal  
locations  as  detailed  in  this  Use  and  Care  
Manual  have  been  met.  Carefully  inspect  the  
entire  venting  and  air  intake  system  for  any  
signs  of  cracks  or  fractures,  particularly  at  
the  joints  between  elbows  or  other  fittings  
and  the  straight  runs  of  vent  pipe.  Check  the  
system  for  signs  of  sagging  or  other  stresses  
in  the  joints  as  a  result  of  misalignment  of  
 
any  components  in  the  system.  If  any  of  
these conditions  are  found,  they  must  be  
corrected  in  accordance  with  the  venting  
instructions  in  this  manual  before  completing  
the  installation  and  putting  the  water  heater  
into  service.
See  the  back  page  of  this  manual  
for  additional  requirements  for  the  
Commonwealth  of  Massachusetts.
NO!
installing  the  drain  tube  to  the  condensation  
trap.    For  horizontal  installation  with  less  
than  10'  (3.1m),  a  94°  elbow  is  required.  
MINIMUM  VENT  LENGTH:  The  venting  
may  be  as  short  as  12"  (30cm),  in  addition  
to  installation  of  one  94°  elbow  and  one  
vent  termination  to  the  outdoors  through  a  
side  wall  (Total  equivalent  vent  length:  30"  
(76cm)).
Notice:  Make  sure  that  the  seam  of  the  inner  
vent  pipe  in  horizontal  runs  is  toward  the  top  
of  the  installation  (see  diagram).
Vent Seam
YES!
9
11/9/2009 3:10:25 PM

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents