Adjustment Of Components; Adjustment Of Water Regulating Valve (Water-Cooled Model Only) - Hoshizaki F-1500MAH Service Manual

Modular flaker
Hide thumbs Also See for F-1500MAH:
Table of Contents

Advertisement

IV. Adjustment of Components

1. Adjustment of Water Regulating Valve (water-cooled model only)

The water regulating valve or also called "water regulator" is factory-adjusted. No adjustment
is required under normal use. Adjust the water regulator , if necessary, using the following
procedures.
1) Attach a pressure gauge to the high-side line of the system. Or prepare a thermometer to
check the condenser drain temperature.
2) Rotate the adjustment screw by using a flat blade screwdriver, so that the pressure gauge
shows 260 PSIG (R-404A models/-F type), or the thermometer reads 100 -104°F, in 5
minutes after the icemaking process starts. When the pressure exceeds 260 PSIG or the
condenser drain temperature exceeds 104°F, rotate the adjustment screw counterclock-
wise.
3) Check that the pressure or the condenser drain temperature holds a stable setting.
43

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

F-1500ma-cF-1500mwhF-1500mw-cF-1500mrhF-1500mr-c

Table of Contents