E. Locating your Fireplace & Chimney
Location of the fi replace and chimney will affect perfor-
mance.
Install within the warm airspace enclosed by the building
envelope. This helps to produce more draft, especially
during lighting and die-down of the fi re.
Penetrate the highest part of the roof. This minimizes the
effects of wind loading.
Locate termination cap away from trees, adjacent
structures, uneven roof lines and other obstructions.
Minimize the use of chimney offsets.
Consider the fi replace location relative to fl oor and ceiling
and attic joists.
Take into consideration the termination requirements in
Section 8 and Section 9.
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Windward
Recommended:
Outside Air Intake
on windward side
Figure 5.1
Recommended Chimney Locations
Recommended Location:
Recommended Location:
• Above peak
• Above peak
• Inside heated space
Marginal Location:
• Below peak
Recommended:
• Insulated exterior chase
in cooler climates
Multi-level Roofs
Heat & Glo • RUTHERFORD-50 • 4059-333 Rev D • 07/08
NOTICE: Locating the fi replace in an area of considerable
air movement can cause intermittent smoke spillage from
fi replace. Do not locate fi replace near
frequently open doors
central heat outlets or returns
DO NOT install in a basement.
Marginal Location:
• Wind loading possible
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Leeward
NOT recommended:
Outside Air Intake
on leeward side
15