E. Locating your Fireplace & Chimney
Location of the fireplace and chimney will affect perfor-
mance.
•
Install within the warm airspace enclosed by the building
envelope. This helps to produce more draft, especially
during lighting and die-down of the fire.
•
Penetrate the highest part of the roof. This minimizes the
effects of wind loading.
•
Locate termination cap away from trees, adjacent
structures, uneven roof lines and other obstructions.
•
Minimize the use of chimney offsets.
•
Consider the fireplace location relative to floor and ceiling
and attic joists.
•
Take into consideration the termination requirements in
Section 8 and Section 9.
Location NOT recommended:
• Not the highest point of the roof
• Wind loading possible
Windward
Figure 5.1
Recommended Chimney Locations
16
Recommended Location:
Recommended Location:
• Above peak
• Inside heated space
• Above peak
Marginal Location:
• Below peak
Recommended:
• Insulated exterior chase
in cooler climates
Multi-level Roofs
Heat & Glo • RUTHERFORD-42 • 4059-309 Rev L • 5/11
NOTICE: Locating the fireplace in an area of considerable
air movement can cause intermittent smoke spillage from
fireplace. Do not locate fireplace near
•
frequently open doors
•
central heat outlets or returns
DO NOT install in a basement.
Marginal Location:
• Wind loading possible
Location NOT recommended:
• Too close to tree
• Below adjacent structure
• Lower roof line
• Avoid outside wall
Leeward