Cautions, Warnings, and Instructions
Wiring Warnings for Electrical Practices and Wire Sizes
The warnings and instructions in this section summarize the procedures necessary to
ensure an inverter installation complies with Underwriters Laboratories®
guidelines.
WARNING: "USE 60/75°C Cu wire only" or equivalent. For models
X200-005S, -007S, -011S, -022S, -007N, -015N, -015L, -022L, -037L, -055L,
-075L.
WARNING: "USE 75°C Cu wire only" or equivalent. For models X200-002S,
-004S, -002N, -004N, -002L, -004L, -007L, -022H, -030H, -037H, -040H,
-055H, 075H.
WARNING: "USE 60°C Cu wire only" or equivalent. For models X200-004H,
-007H, and -015H.
WARNING: "Open Type Equipment"
WARNING: "Suitable for use on a circuit capable of delivering not more than
100k rms symmetrical amperes, 240V maximum when protected by Class CC,
G, J or R fuses or circuit breaker having an interrupting rating not les than
100,000 rms symmetrical amperes, 240 volts maximum". For models with
suffix S, N or L.
WARNING: "Suitable for use on a circuit capable of delivering not more than
100k rms symmetrical amperes, 480V maximum when protected by Class CC,
G, J or R fuses or circuit breaker having an interrupting rating not les than
100,000 rms symmetrical amperes, 480 volts maximum." For models with
suffix H.
WARNING: "Install device in pollution degree 2 environment."
WARNING: "Maximum Surrounding Air Temperature 50°C". or equivalent.
WARNING: "Caution-Risk of electric shock⎯capacitor discharge time is at
least 5 minutes."
WARNING: "Solid state motor overload protection is provided in each model".
WARNING: "Integral solid state short circuit protection does not provide
branch circuit protection. Branch circuit protection must be provided in
accordance with the National Electric Code and any additional local codes" or
equivalent.
- 22 -