Temperature Pressure Relief Valve - Kenmore Power Miser 1533.31412 HA Owner's Manual

Gas water heater
Table of Contents

Advertisement

Look atthetopofthewater h eater. Thecold water i nlet i s
marked "COLD". Put t wo orthree turns ofteflon tape
around
the threaded
end of the threaded-to-sweat
coupling and
around both ends of the 3/4" NPT threaded
nipple. Using
flexible connectors,
connect the cold water pipe to the cold
water inlet of the water heater.
NOTE: This water heater is super insulated
to minimize
heat loss from the tank. Further reduction
in heat loss
can be accomplished
by insulating the hot water lines
from the water heater.
INSTALLATION
COMPLETED USING
INSTALLATION
KIT
FLEXIBLE
WATER
CONNECTORS
HOT WATER
OUTLET
l
l
SHUTOFF
VALVE
THREADEDTO
THREADEDTO
COLD WATER
{NLET
SWEAT COUPLING
SWEAT
COUPLING
314"THREADED
_
HEATTRAPWITH
_
_
3_ I'THREADED
SECONDARY
COUPLING/HEATTRAP
ANODE
DRAFTHOOD
TEMPERATURE-
9F--PRESSURE
RELIEF VALVE
DISCHARGE
PIPE
(Do not cap or plug)
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified
by a nationally
recognized
testing
laboratory that maintains periodic inspection
of production of
listed equipment of materials as meeting the requirements
for
Relief Valves and Automatic Gas Shutoff Devices for Hot Water
Supply Systems, ANSI Z21,22 and the code requirements of
ASME,
If replaced,
the valve must meet the requirements
of local
codes,
but not less than a combination
temperature
and
pressure
relief
valve
certified
as indicated
in the above
paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035kPa) and a discharge capacity not less
than the water heater input rate as shown on the model rating
plate.
For safe operation of the water heater, the relief valve must not
be removed from its designated opening nor plugged,
The temperature-pressure
relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward
and provide tubing so that any
discharge will exit only within 6 inches (153 mm) above, or at
any distance below the structural floor, see Figure 16. Be certain
that no contact
is made with any live electrical
part.
The
discharge
opening
must not be blocked
or reduced in size
under any circumstances.
Excessive
length, over 30 feet
(9.14 m), or use of more than four elbows can cause restriction
and reduce the discharge capacity of the valve.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided.
To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed
to discharge
water
in quantities
should
circumstances
demand.
If the discharge pipe is not connected
to a drain or other suitable means, the water flow may cause
property damage.
FLOOR DRAIN
FIGURE15.
Temperature-Pressure
Relief Valve
Explosion
Hazard
Temperature-pressure
relief valve
must comply
with ANSi
Z21.22
and ASME code,
Properly
sized
temperature-
pressure
relief
valve
must
be
installed in opening provided.
Can result
in overheating
and
excessive
tank pressure.
Can cause serious injury or death.
Water Damage
Hazard
•Temperature-pressure
relief valve discharge
pipe must terminate at adequate drain•
13
The Discharge Pipe:
• Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
• Shall not be plugged or blocked.
• Shall be of material listed for hot water distribution.
• Shall be installed so as to allow complete drainage of both
the temperature-pressure
relief valve, and the discharge
pipe.
• Shall terminate at an adequate drain.
• Shall not have any valve between the relief valve and tank.

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents