Temperature-Pressure Relief Valve - Kenmore Elite 153.321161 Use & Care Manual

Hybrid electric water heater
Table of Contents

Advertisement

Temperature=Pressure
Relief Valve
Explosion
Hazard
Temperature-pressure
relief valve
must comply
with ANSI Z21.22
CSA 4.4 andASME
code.
• Properly sized temperature-relief
valve must be installed in opening
provided.
• Can result
in overheating
and
excessive tank pressure.
• Can cause serious injury or death.
This heater is provided with a properly certified combination
temperature - pressure relief valve by the manufacturer.
The valve is certified by a nationally recognized testing laboratory
that maintains periodic inspection of production of listed equipment
of materials as meeting the requirements for Relief Valves for Hot
Water Supply Systems, ANSI Z21.22 • CSA 4.4, and the code
requirements of ASME.
If replaced, the valve must meet the requirements of local codes,
but not tess than a combination temperature and pressure relief
valve certified as indicated in the above paragraph.
The valve must be marked with a maximum set pressure not to
exceed the marked hydrostatic working pressure of the water
heater (150 psi = 1,035 kPa) and a discharge capacity not less
than the water heater input rate as shown on the model rating plate.
(For electric heaters, watts x 3.412 equals Btu/hr input rate)
For safe operation of the water heater, the relief valve must not be
removed from its designated opening nor plugged.
The temperature-pressure
relief valve must be installed directly
into the fitting of the water heater designed for the relief valve.
Position the valve downward
and provide tubing so that any
discharge will exit only within 6 inches (153 mm) above, or at any
distance below the structural floor. Be certain that no contact is
made with any live electrical part. The discharge opening must
not be blocked or reduced in size under any circumstances.
Excessive length, over 30 feet (9.14 m), or use of more than four
elbows can cause restriction and reduce the discharge capacity
of the valve.
Water Damage
Hazard
- Temperature-pressure
relief valve discharge
pipe must terminate at adequate drain.
No valve or other obstruction is to be placed between the relief
valve and the tank. Do not connect tubing directly to discharge
drain unless a 6 inch air gap is provided.
To prevent bodily
injury, hazard to life, or property damage, the relief valve must
be allowed to discharge water in quantities should circumstances
demand. Ifthe discharge pipe is not connected to a drain or other
suitable means, the water flow may cause property damage.
The Discharge Pipe:
Shall not be smaller in size than the outlet pipe size of the
valve, or have any reducing couplings or other restrictions.
Shall not be plugged or blocked.
Shall be of material listed for hot water distribution.
Shall be installed so as to allow complete drainage of both the
temperature-pressure
relief valve, and the discharge pipe.
Shall terminate a maximum of six inches above a floor drain or
external to the building.
In cold climates, it is recommended
that the discharge pipe be terminated at an adequate drain
inside the building.
Shall not have any valve between the relief valve and tank.
Water
temperature
over
125°F
(52°0) can cause severe burns
instantly resulting in severe injury
or death.
Children,
the
elderly,
and the
physically
or mentally
disabled
are at highest riskfor scald injury.
Feel
water
before
bathing
or
showering.
Temperature
limiting valves are
available.
Read instruction
manual for safe
temperature setting
The temperature-pressure
relief valve must be manually operated
at least once a year.
Caution should be taken to ensure that
(1) no one is in front d or around the outlet of the temperature-
pressure relief valve discharge line, and (2) the water manually
discharged will not cause any bodily injury or property damage
because the water may be extremely hot.
If after manually operating the valve, it fails to completely reset
and continues to release water, immediately close the cold water
inlet to the water heater, follow the draining instructions, and
replace the temperature-pressure
relief valve with a new one.
TeemsPs: rr:tRr:ll:f da iv e _
Discharge
Pipe
(Do Not Ptug or Cap)
Drain Pan 2 1/2"
DtP_t_eMs axldeU'_h: _d
_
the water heater.
'_
U
Drain Line _-_3/4 "_
ID Minimum
_"---_
6_' M aximum
Drain
Air Gap
FIGURE 12.
14

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Elite 153.321181

Table of Contents