specifications apply to all three axes. For vibration testing methods, see ASTM D999-91 Standard
Methods for Vibration Testing of Shipping Containers.
Table 8 Mechanical vibration specifications
Condition
Operating
Nonoperating
Shipping and storage (product packed in
factory packing)

Shock specifications

Table 9
lists shock specifications. For horizontal shock testing methods, see ASTM D5277-92 Standard
Test Methods for Performing Programmed Horizontal Impacts Using an Inclined Impact Tester. For
vertical shock testing methods, see ASTM D6055-96 Standard Test Methods for Mechanical Handling
of Unitized Loads and Large Shipping Cases and Crates.
Table 9 Shock specifications
Condition
Operating
Nonoperating
Shipping and storage (product packed in factory
packing)

Heat dissipation, power consumption, and air flow specifications

Table 10
describes the heat dissipation and power consumption of the XP10000 disk array when
loaded with the maximum number of disk drives.
Table 10 Maximum heat and power specifications
Parameter
Power consumption
(kVA)
Heat dissipation
(kW)
BTUs per hour
Kcal per hour
Specification
0.25 mm, 5–10 Hz
0.05 G, 10–300 Hz
2.5 mm, 5–10 Hz
0.5 G, 10–70 Hz
0.05 mm, 70–99 Hz
1.0 G, 99–300 Hz
0.5 G, 15 minutes (at four most severe resonances between
5–200 Hz)
Specification
None
8 G, 15 ms
Horizontal: Incline impact: 1.22 m/s
Vertical: Rotational edge: 0.1 m
Primary Rack
Second Rack
4.9
4.6
15710
3959
XP10000 Disk Array Site Preparation Guide
Full array
3.2
3.0
10246
25955
2582
6541
8.1
7.6