3.
Sheet steel chimney connector, min. 24
gauge in thickness, with a ventilated
thimble, min. 24 gauge in thickness, having
two 1" (25mm) air channels, separated from
combustibles by a min. of 6" (150mm) of
glass fibre insulation. Opening should be
covered and thimble supported with a sheet
steel support, min. 24 gauge in thickness.
Supports should be securely fastened to
wall surfaces on all sides and should be
sized to fit and hold chimney section.
Fasteners used to secure chimney sections
should not penetrate chimney flue liner.
(25mm)
(150mm)
glass fibre insulation
Fig.12
4.
Solid insulated listed factory-built chimney
length with an inside diameter 2" (50mm)
larger than the chimney connector and hav-
ing 1" (25mm) or more of insulation, serving
as a pass-through for a single wall sheet
steel chimney connector of min. 24 gauge
thickness, with a min. 2" (50mm) air space
between the outer wall of chimney section
and combustibles. Min. length of chimney
section shall be 12" (305mm). Chimney sec-
tion concentric with and spaced 1" (25mm)
away from connector by means of sheet
steel support plates on both ends of chimney
section. Opening shall be covered and chim-
ney section supported on both sides with
sheet steel supports of min. 24 gauge thick-
ness.
Supports should be securely fastened to wall sur-
faces on all sides and shall be sized to fit and hold
chimney section. Fasteners used to secure chimney
sections should not penetrate chimney flue liner.
(50mm)
(25mm) constructed of
9
(50mm)
Minimum clearances 2"(50mm)
1" (50mm)
air space to
chimney
length
Fig.13

MASONRY FIREPLACE

Before the installation the entire fireplace system
should be inspected for condition and code
compliance prior to connecting to the fireplace chim-
ney. Older fireplaces and chimneys may not have
been constructed to current-day codes.
The fireplace and chimney should be in, or brought
up to, acceptable conditions and proper clearances
should be met before connecting to the fireplace
chimney.
The size of the flue must be considered. If the
fireplace chimney is too large, a relining system may
be installed using an approved relining system.
Fig.14
Air space 2" (50mm)