Table Of Contents; Filter/Stand Section - Greenheck VSU 457831 Installation, Operation And Maintenance Manual

Vsu make-up air unit
Table of Contents

Advertisement

Table of Contents

Installation
Filter/Stand Section . . . . . . . . . . . . . . . . . . . . . . 3-4
Burner/Blower Section . . . . . . . . . . . . . . . . . . . . . 4
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Dimensional Data . . . . . . . . . . . . . . . . . . . . . . . . . 5
Direct Gas Piping . . . . . . . . . . . . . . . . . . . . . . . . 6-7
Start-Up
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8-9
Direct Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10-12
Operation
Electrical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Blower . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Heater . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-17
Maintenance
Routine . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18-19
Fall . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Typical Control Center Layout . . . . . . . . . . . . . . 20
Typical Gas Train Layout . . . . . . . . . . . . . . . . . . . 20
Start-Up Check List . . . . . . . . . . . . . . . . . . . . . . 21
Maintenance Log . . . . . . . . . . . . . . . . . . . . . . 22-23
Warranty . . . . . . . . . . . . . . . . . . . . . . . . .Backcover
® ® ® ® ®
Installation

1. Filter/Stand Section

The unit should be mounted on a concrete slab four
inches thick with a proper gravel drainage bed. Allow
one foot on each side of the unit as shown in the
Concrete Slab and Unit Footprint drawing below.
Concrete Slab Dimensions
Housing Size
A
B
C
D
E
All dimensions are shown in inches.
Building Wall
Approx. Stand Feet Locations
Concrete Slab
D
A
12
12
Concrete Slab and Unit Footprint
The filter section ships inside the stand (see drawing
on next page). After the unit is set on the slab, it can
be anchored through the stand feet. The unit footprint
of the unit is shown above.
Greenheck recommends having a three foot clearance
on the controls side and a two foot clearance on the
other three sides of the unit for serviceability.
The following statement pertains to direct gas units
only. When ordered with insulation, this unit has a
zero-inch clearance tolerance to any combustibles,
on all sides and top. Without insulation, the clearance
tolerance is six inches.