Heater - Greenheck VSU 457831 Installation, Operation And Maintenance Manual

Vsu make-up air unit
Table of Contents

Advertisement

Troubleshooting
Heater Does Not Operate
Visible pilot
Measure the flame signal
when there is a visible pilot
Flame signal greater
than 1.25 VDC
Yes
Check for proper airflow
(Direct Gas Start-Up Step #3)
Pressure drop across the burner
between 0.625 and 0.675 in. wc?
Yes
Check the minimum firing rate
(Direct Gas Start-Up Step #4
Is the minimum firing rate
set correctly?
Yes
Does the flame signal
remain constant?
Yes
® ® ® ® ®
Note: The flame signal should be steady and
above 1.25 VDC with a visible pilot.
(Reference Direct Gas Start-Up – Step #7)
No
(Adjust the flame rod to avoid contact with the burner or the unit)
Note: When the pressure is low or marginal and the unit
begins heating, the air density will change. This can cause
the pressure to drop below the minimum setting. Also, low
airflow can cause the flame to walk out of the burner and
away from the flame sensor, causing the unit to recycle.
No
(Reference Direct Gas Start-Up – Step #3)
No
(Reference Direct Gas Start-Up – Step #4)
No
If the signal slowly drops off, typically the airflow is too low
(Reference Blower Start-Up – Step #4)
If it suddenly drops to zero, the flame rod is grounding out
(Adjust the flame rod to avoid contact with the burner or the unit)
If the flame signal is above 1.25 VDC and constant,
the main gas valves will remain open until the call
for heat is interrupted or the unit is shut down.
Unit is not grounded
(Properly ground unit)
Flame rod is grounding out
Cracked porcelain on flame rod
(Replace flame rod)
Adjust burner baffles
Adjust the minimum firing rate
17