Combustion And Ventilation Air - COZY VC501A Installation And Operation Instructions Manual

Gas-fired vented room heater
Table of Contents

Advertisement

COMBUSTION
AND VENTILATION
AIR
When installed, this gas appliance
must be provided with fresh air for
combustion, ventilation, and dilution of hot flue gases. The minilnum required
volume of the area where the appliance is installed should be 50 cubic feet per
1,000 btu/hr.
If installed in an area of the home that is considered an unconfined space, the
natural infiltration of air around windows and doors will be adequate. If the
area is considered a confined space (less than 50 cubic feet per thousand btu),
tiesh air can be supplied by providing two permanent openings into adjoining
rooms. Each opening shall have a lninilnum free area of one square inch per
1,000 bm per hour of the total input rating of all gas appliances in the confined
space, but not less than 100 square inches. One of the openings shall be within
12 inches of the ceiling and one within 12 inches of the floor. See Figmre A.
If the home is ofunusually tight construction (new and remodeled homes), tiee
air must be supplied
through opening(s)
to the outdoors.
This can be
accomplished by providing 2 permanent openings, one commencing within 12
inches of the ceiling and one within 12 inches of the floor. These openings
shall comlnunicate directly with the outdoors, or spaces that comlnunicate
freely with the outdoors, such as a ventilated attic and crawl space through
galvanized or equivalent corrosion-resistant
ducts. Exception: unobstructed
stud and joist spaces are acceptable ducts provided that not more than one tire
block is removed. Special provisions must be taken to insure that these stud
and joist spaces cannot be blocked with insulation or other objects. Each of
these openings using vertical ducts shall have a minilnum free area of one
square inch per 4,000 btu/hr of total input rating of all gas appliances.
See
Figmre B and C. If horizontal ducts are used, the minimum tiee area shall be one
square inch per 2,000 btu/hr of total input rating of all gas appliances.
Fresh make-up air can also be provided through a duct to one permanent
opening commencing within 12 inches of the ceiling. The minimuln tiee area of
this opening shall be one square inch per 3,000 btu/hr of the total input rating
ofalt gas appliances but not less than the sum of the areas of all vent connectors
in the space. See Figure D.
When calculating the amount of fresh air needed you must include make-up air
requirements for the operation of exhaust tans, kitchen ventilation systems,
clothes dryers, and fireplaces.
Additional intbnnation
can be t\_und in the latest edition of ANSI Z223.1
(National Fuel Gas Code).
ALL COMBUSTION
AIR FROM OUTDOORS
THROUGH VENTILATED
ATTIC
UL Listed Vent Cap
Gas Vent
(each end of attic)
Outlet
Air
Inlet Air Duct (Ends 1 Ft.
[300 1rim] above floor)
ALL COMBUSTION AIR FROM
ADJACENT INDOOR SPACES
THROUGH INDOOR COMBUSTION
AIR OPEN1NGS
Listed Vent Cap
Opening
FIGURE A
ALL COMBUSTION
AIR FROM
OUTDOORS.
INLET AIR FROM
VENTILATED CRAWL SPACE AND
OUTLET AIR TO VENTILATED
ATTIC
/UL Listed Vent Cap
' pUL Listed Gas Vent
Ventilation
Louvers
,_
_1[_1
end of attic"
II Irr .
-,,-!,==
Outlet
Air
-'-Inlet Air
.........
l,l,,,f
• --
Uventilation-
louvers for unheated
crawl space
FIGURE B
ALL
COMBUSTION
AIR FROM
OUTDOORS
THROUGH
SINGLE
COMBUSTION
AIR OPENING
• UL Listed Vent
Opening
Alternate
opening
location
FIGURE C
Page 6
FIGURE D

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents