COZY VFT201 Installation And Operation Instructions Manual page 8

Vet free infra red heaters
Table of Contents

Advertisement

TABLE
1 - first stage
pipe sizing
10 PSIG
Inlet with
a 1 PSIG
Pressure
Drop
Maximum
capacity of pipe or robing,
in thousands
ofBTU/hr,
of L.P. Gas
PROPANE
GAS
Size of Pipe
LENGTH OF PIPE OR TUBING. FEET*
Or Copper
Tubing, Inches
10
20
30
40
50
60
70
80
90
100
Copper
Tubing
(OD
Pipe
Size
3/8
558
383
309
265
235
213
196
182
171
161
½
1387
870
700
599
531
481
443
412
386
365
5/8
2360
1622
1303
1115
988
896
824
767
719
679
¾
3993
2475
2205
1887
1672
1515
1394
1297
1217
1149
½
3339
2295
1843
1577
1398
1267
1165
1084
1017
961
¾
6982
4799
3854
3298
2923
2649
2437
2267
2127
2009
1
13153
9040
7259
6213
5507
4989
4590
4270
4007
3785
1-1/4
27004
18560
14904
12756
11306
10244
9424
8767
8226
7770
1-1/2
40461
27809
22331
19113
16939
15348
14120
13136
12325
11642
2
77924
53556
43008
36809
32623
29559
27194
25299
23737
22422
Copper
Tubing
(O.D.)
Pipe
Size
12s
IS0
17s
?00
?2s
?sO
?Ts
_00
_s0
400
3/8
142
130
118
111
104
90
89
89
82
76
½
323
293
269
251
235
222
211
201
185
172
5/8
601
546
502
467
438
414
393
375
345
321
¾
1018
923
843
790
740
700
664
634
584
543
½
852
772
710
660
619
585
556
530
488
454
¾
1780
1613
1484
1381
1296
1224
1162
1109
1020
949
1
3354
3039
2796
2601
2441
2305
2190
2089
1922
1788
1-1/4
6887
6240
5741
5340
5011
4733
4495
4289
3945
3670
1-1/2
10318
9349
8601
8002
7508
7092
6735
6426
5911
5499
2
19871
18005
16564
15410
14459
13658
12971
12375
11385
10591
*Total length
away).
Notes:
1)
2)
of piping fronl outlet of first stage regulator
to inlet of second stage regulator
(or to inlet of second stage regulator
furthest
To allow 2 PSIG pressure drop, multiply total gas demand by .707, and use capacities
fronl table.
For different first stage pressures,
multiply total gas demand by the i\311owing factors, and use capacities
from table.
First State Pressure
PSIG
Multiply
by
20
.844
21
.912
Data Calculated
per NFPA #54 & 58.
TABLE
4 - Second,
Single,
or Integral
Twin
Stage
Pipe
Sizing
11 Inches Water Column Inlet with a V2Inch Water Column Drop
Maximum capacity of pipe oi tubing in thousands ofBTU/hr of LP-Gas
PROPANE GAS
Size of Pipe
Or Copper
Tubing, Inches
3/8
Copper
1/2
Tubing
5/8
(OD.)
Pipe
Size
Copper
Tubing
(OD.)
Pipe
Size
3/4
7/8
1/2
3/4
1
1-1/4
1-1/2
2
3/8
1/2
5/8
3/4
7/8
1/2
3/4
1
1-1/4
1-1/2
2
LENGTH
OF PIPE OR TUBING.
FEET*
10
20
30
40
50
60
70
80
49
34
27
23
20
19
110
76
61
52
46
42
38
36
206
141
114
97
86
78
71
67
348
239
192
164
146
132
120
113
536
368
296
253
224
203
185
174
291
200
161
137
122
110
102
94
608
418
336
287
255
231
212
198
1146
788
632
541
480
435
400
372
2353
1617
1299
1111
985
892
821
764
3525
2423
1946
1665
1476
1337
1230
1144
6789
4666
3747
3207
2842
2575
2369
2204
90
33
62
105
161
87
185
349
717
1074
2068
125
150
175
200
225
250
275
300
350
74
67
62
58
54
51
48
46
43
155
141
129
120
113
107
101
97
89
292
265
244
227
213
201
191
182
167
600
544
500
465
437
412
392
374
344
899
815
749
697
654
618
587
560
515
1731
1569
1443
1343
1260
1190
1130
1078
992
*Total length of piping
100
32
59
100
154
84
175
33O
677
1014
1954
4OO
40
83
156
320
479
923
from outlet of regulator
to appliance
furthest
away.
Data Calculated
per NFPA #54 & 58.