MAINTENANCE
Section 4 - Maintenance
15 kW Generator
_RANK
This
ieature
prevents
tlle
generator
irom
damaging
itself
when
it continually
attempts
to start
and
anoth-
er problem,
such
as no fllel
supply,
prevents
it from
starting.
Tile unit
will crank
and
rest
Ihr a preset
time
limit.
Then,
it will
stop
cranking,
and
the
LED
will
light
indicating
an overcrank
failure.
The
AUTO/OFF/
MANUAL
switch
will
need
to be
set to OFF
and
then
back
to AUTO
to reset
the generator
control
board.
NOTE:
If the
fault
is not repaired,
the
overcrank
feature
will continue
to activate.
3.7,3.1
Approximate
Crank Cyde Times
* 15 seconds
ON
. 7 seconds
OFF
. 7 seconds
ON
. 7 seconds
OFF
. Repeat
Ior 45 seconds
Approximately
90 seconds
total
3.Z4
OVERSPEED
This
ieature
protects
the
generator
from
damage
by
shutting
it down
if it happens
to ruts
faster
than
the
preset
limit.
This
protection
also
prevents
the genera-
tor
from
supplying
an
output
that
could
potentially
damage
appliances
connected
to
the
generator
cir-
cuit.
Contact
the nearest
dealer
if this
failure
occurs.
4.1
FUSES
The
generator
panel's
15 amp
fuse
(Figure
4.1)
pro-
tects
the DC control
circuit
against
overload.
The
fllse
is wired
its series
with
the battery
output
lead
to the
panel.
If the fllse element
has melted
open,
the engine
cannot
crank
or start.
Replace
the fuse
using
only
an
identical
15-amp
replacement.
The
generator
panel's
7.5
amp
fllse
protects
the
12
VDC accessory
socket.
If the fllse element
has
melted
open,
the
12 VDC
socket
will
not
provide
power
to
any
accessories.
Replace
the/ilse
using
only
an iden-
tical
7.5 amp
replacement.
To remove
fuse,
push
the
Iuse
holder
cap
down
and
rotate
counterclockwise.
Figure
4. ! - Generator
Contro!
Pane!
0UTLETFUSE
?;
AUTO
OFF
SYSTEM FUSE
O
15A
SET
EXERCISE
TIME
16
4.2
CHECKING THE ENGINE
OiL LEVEL
For
oil capacities,
see
the
"Specifications,"
Section.
For
engine
oil recommendations,
see
Section
4.3.1.
_[% check
the
engine
oil
level,
proceed
as
iollows
{Figure
4.2):
1.
Start
the
generator
by
moving
the
AUTO/OFF/
MANUAL
switch
to the
IVIANUAL position.
Allow
it to run
for a short
while
and
then
shut
it down
by moving
the switch
to the OFF position.
2.
Remove
the dipstick
and
wipe
it dry with
a clean
cloth.
3.
Install
the dipstick;
then,
remove
it again.
The
oil
level
should
be at the dipstick
"l_5lll" mark.
If nec-
essary,
add
oil to the
"b)lll"
mark
only.
DO
NOT
FILL ABOVE
THE
"FULE'
MARK.
CAUTION
/_
Never operate the engine with the oil JevM
bMow the "Add"
mark on the dipstick.
Doing
this could damage
the engine.
4.
Install
the dipstick.
5.
Reset the AUTO/OFF/MANUAL
switch
to its origi-
nal position.
Figure
4.2 -- Oi[ Dipstick
and Fill, !5 kW
Oil Dipstick
4.3
CHANGING THE ENGINE OIL
4.3.1
ENGINE OIL RECOMMENDATIONS
Use
oil of American
Petroleum
Institute
(API)
Service
Class
SG,
SH
or
SJ.
Use
all
season
SAE
5W-30
Synthetic
oil. Organic
break-in
oil is required
before
using
sy_sthetic
oil.
NOTE:
The
unit
is supplied
with
"break-in"
oil. See
the
"Break-in
Procedure"
Section
for the first required
oil change.