CONTROL
OPERATION
Complete
C Control
Indicators
-- The status
LED
on the Complete
C control displays file current status of the
Complete
C control. If in Test mode, the LED will flash the
code of the last fault and the almm relay will cycle the stone
number as the fault code. See Table 4.
There are 2 categories
of fault types: primary and second-
ary. Primaly
fault types include
High Pressure
(HI)), Low
Pressure (LP), Water Coil Freeze
Protection
(FPI),
Air Coil
Freeze Protection
(FP2), and Condensate
Overflow
(CO). If
fault type is primary,
it is always
stored in memory.
Primary
faults override
secondary
faults. Secondary
fimlt types are:
Over/Under
Voltage
Shutdown
and Performance
Monitor
(PM). Secondary
faults are retained
in memory
only if there
are not any primary
faults. Secondary
faults will not over-
write primary
fimlts. See Table 5.
Table 4 -- Complete C Control Current LED Status
and Alarm Relay Operations
DESCRIPTION OF
OPERATION
Normal Mode
Normal Mode with
PM Warning
Complete C Control is
non-functional
Fault Retry
Lockout
Over/Under Voltage
Shutdown
LED STATUS
On
Off
Slow Flash
Fast Flash
Slow Flash
Test Mode --
No Fault in Memory
Flashing
Code
1
Test Mode --
HP Fault
in Memory
Flashing
Code 2
Test Mode --
LP Fault
in Memory
Flashing
Code 3
Test Mode --
FP1 Fault
in Memory
Flashing
Code 4
Test Mode --
FP2 Fault
in Memory
Flashing
Code 5
Teat Mode --
CO Fault
in Memory
Flashing
Code 6
Teat Mode
-- Over/Under
Flashing
Code 7
Shutdown
in Memory
Teat Mode -- PM in Memory
Flashing
Code 8
Teat Mode -- FPI/FP2
Swapped
Fault in Memory
Flashing
Code 9
ALARM
RELAY
Open
Cycle
(closed
5 sec,,
Open 25 sec.)
Open
Open
Closed
Open
(Closed
after
15 minutes)
Cycling
Code 1
Cycling
Code 2
Cycling
Code 3
Cycling
Code 4
Cycling
Code 5
Cycling
Code 6
Cycling
Code 7
Cycling
Code 8
Cycling
Code 9
LEGEND
CO
--
Condensate
Overflow
FP
--
Freeze
Protection
HP
--
High Pressure
LED
--
Light-Emitting
Diode
LP
--
Low Pressure
PM
--
Performance
Monitor
NOTES:
1. Slow flash is 1 flash every 2 seconds.
2. Fast flash is 2 flashes
every
1 second.
3. EXAMPLE:
"Flashing
Code
2" is represented
by 2 fast flashes
fol-
lowed
by a 10-second
pause.
This sequence
will repeat continually
until the fault is cleared.
Table 5 -- Complete C Control LED Code and
Fault Descriptions
LED
FAULT
DESCRIPTION
CODE
1
No fault in memory
There has been no fault since
the last power-down to power-
up sequence
2
High-Pressure Switch
HP Open Instantly
3
Low-Pressure Switch or LP open for 30 continuous sec-
LOC
onds before or during a call
(bypassed for first 120 seconds
of operation)
4
Freeze Protection Coax
FP1 below Temp limit for 30
-- FP1
continuous seconds (bypassed
for first 120 seconds of
operation)
5
Freeze Protection Air
FP2 below Temp limit for 30
Coil -- FP2
continuous seconds (bypassed
for first 120 seconds of
operation)
6
Condensate overflow
Sense overflow (grounded) for
30 continuous seconds
7
Over/Under Voltage
"R" power supply is <8 vac or
(Autoreset)
Shutdown
>365 vac
8
PM Warning
Performance Monitor Warning
has occurred.
9
FP1 and FP2 Ther-
FP1 temperature is higher than
mistors are in Reverse
FP2 in Heating/Test mode, or
Positions
FP2 temperature is higher than
FP1 in Cooling test mode.
LEGEND
CO
--
Condensate
Overflow
FP
--
Freeze Protection
HP
--
High Pressure
LED
--
Light-Emitting
Diode
LOC
--
Loss of Charge
Switch
PM
--
Performance
Monitor
Complete
C and Deluxe D Controls
-- The follow-
ing operations
are common to both Complete
C and Deluxe D
coutrol
S.
TEST MODE --
Test mode provides
the ability to check the
control operation
in a timely
mmmel: The control
enters a
20-minute
Test mode by momentarily
shorting the test termi-
nals. All time delays are sped up 15 times.
To enter Test mode, cycle the power 3 times within 60 sec-
onds or monentarily
sholt the test terminals.
The LED will
flash a code representing
the last fault when entering the Test
mode. Tile alarm relay will also power on and off during Test
mode. See Table 3. To exit Test mode, sholl the terminals for 3
seconds or cycle file power 3 times within 60 seconds.
NOTE:
The flashing code and _darm relay cycling code will
both have the same numerical
label. For example,
flashing
code 1 will have an alarm relay cycling
code 1. Code 1 indi-
cates the control
has not faulted since the last power off to
power on sequence.
RETRY MODE --In
retry mode, the status LED will start to
flash slowly (one flash every two seconds)
to signal that the
control is trying to recover from ml input fault. The control will
stage off file outputs
mad try to again satisl_
the thermostat
used to terminal Y. Once the thermostat
input calls are satis-
fied, the control will continue normal operation.
NOTE:
If 3 consecutive
faults occur without
satisfying
the
thermostat
input c_dl to terminal
_ the control will go into
lockout mode. Tile last fault causing
the lockout
is stored in
memory and can be viewed
by entering Test mode.
If one try is selected for FPI and FP2 then there will be no
letries for FPI and FP2 faults.
POWER UP MODE -- The unit will not operate until all the
inputs, terminals
and safety controls
me checked
for normal
operation.
NOTE: The compressor
will have a 5 minute anti-sholt
cycle
upon power up.
11