Typical Wiring Schematics - Carrier AQUAZONE 50KQL07-19 Product Data

Water source heat pumps console unit
Hide thumbs Also See for AQUAZONE 50KQL07-19:
Table of Contents

Advertisement

Typical wiring schematics

PUSH BUTTON SWITCH ATTRIBUTES
X = CLOSED
TERMINALS
1
2
3
4
1A 1B 2A 3A 4A 5A 6A 7A 8A
STOP
X O O O O O O O O
FAN ONLY
X O O O O X O O O
LOW FAN
X O X
X
X O X O O
HIGH FAN
X O X
X
X O O X
BLOWER MOTOR WIRING
UNIT SIZE POLE A
POLE B
07
5
3
09
5
4
12
4
3
15
4
3
19
4
3
GROUND
PB
CAP
COMPLETE
C
CONTROL
UMT
AL
Alarm Relay Contacts
BM
Blower Motor
BR
Blower Relay
CAP
Capacitor
CB
Circuit Breaker
CO
Sensor, Condensate Overflow
CR
Compressor Relay
DM
Damper Motor
FP1
Sensor, Water Coil Freeze Protection
FP2
Sensor, Air Coil Freeze Protection
HP
High-Pressure Switch
JW1
Jumper Wire for Alarm
LOC
Loss of Charge Pressure Switch
PB
Power Terminal Block
PBS
Push Button Switch
PM
Performance Monitor
RVS
Reversing Valve Solenoid
TRANS —
Transformer
UMT
Unit Mounted Thermostat
WV
Water Valve
----------
Field Line Voltage Wiring
Field Low-Voltage Wiring
Printed Circuit Trace
MANUAL CHANGEOVER WITH COMPLETE C CONTROLLER
POWER SUPPLY
REFER TO DATA PLATE
USE COPPER
CONDUCTORS ONLY.
SEE NOTE 2
REFER TO DISCONNECT
BOX FOR OPTIONAL
POWER SUPPLY CONNECTION
OPTIONAL
CORD
CONNECTION
O = OPEN
5
6
7
8
CB*
24V
X
BLU
BRN
BRN
BRN
YEL
BR2
BR1
YEL
2
2A
YEL
1
RED
UMT
PBS
ORG
2
3
3
3A YEL
RED
RED
RED
5
5A
RED
RED
BRN
GRY
6
6A
RED
YEL
RED
7A
7
BRN
1
1A
RED
YEL
DM
1B
YEL YEL
ORG
BRN
WV
TRANSFORMER
CR
BR1
BR2
PBS
LEGEND
GROUND
NEUTRAL ON 265V
SYSTEMS
RED
L2
L1
L2 (ribbed)
GROUND
L1 (plain)
SEE
NOTE 3
BLK
TRANS
ORG
230V
SEE
1
0
NOTE 7
CR
BRN
BR
BRG
CCG
CC
C
TEST PINS
COMPR.
R
RELAY
SEE
NOTE 4
Y
JW3
FP1
JW2
Y
FP2
W
DIP SWITCH
1
PM: DISABLED/
O
ENABLED
G
2
STAGE 2: 2/1
3
NOT USED
R
4
NOT USED
C
5
FP1/FP2
JW1
FAULTS: 3/1
AL1
OFF ON
STATUS
AL2
G
LED
SEE
ALARM
A
NOTE 6
COMPLETE C
RELAY
P1
MICRO-
PROCESSOR
CONTROL
LOGIC
Relay/Contactor Coil
Solenoid Coil
Thermistor
Circuit Breaker
Relay Contacts-N.O.
Switch-Temperature
Switch-High Pressure
Switch-Low Pressure
Ground
Wire Nut
Mate-N-Lock
COMPRESSOR
H
BLU
S
CAP
R
8
6
C
C
RED
RED
CR
F
2
4
BLK
BLK
2
B (HIGH)
BRN
BM
YEL
A (LOW)
1
BLK
RED
BLK
5
5A
RED
6
6A
BLK
BLK
7A
7
PBS
TRANSFORMER PRIMARY
SEE
LEAD COLORS
NOTE 7
VOLTAGE
LEAD COLOR
115
YEL
208
230
265
RED
1
HP
HP
RED
2
3
BLU
LOC
LOC
BRN
4
GRY
5
FP1
FP1
6
GRY
SEE
NOTE 4
7
VIO
FP2
FP2
VIO
8
BRN
9
RV
RVS
ORG
10
NOT USED
CO12
YEL
CO
P2
24V
DC
EH1
EH2
CO
P3
*Optional wiring.
NOTES:
1. Compressor and blower motor thermally pro-
tected internally.
2. All wiring to the unit must comply with local
codes.
3. Transformer is wired to 115-V (WHT) lead for
115/1/60 units, 265-V (BRN) lead for 265/1/60
units or 208-V (RED) lead for 208/1/60 units.
For 203/1/60 switch RED and ORG leads at L1
and insulate RED lead.
Transformer is energy limiting or may have circuit
breaker.
4. FP1 thermistor provides freeze protection for
WATER. When using ANTI-FREEZE solutions,
cut JW3 jumper.
5. Typical unit-mounted thermostat wiring shown.
6. 24-V alarm signal shown. For dry alarm contact,
cut JW1 jumper and dry contact will be available
between AL1 and AL2.
7. Transformer secondary ground via Complete C
board standoffs and screws to control box.
(Ground available from top two standoffs as
shown.)
WHT
RED
ORG
BRN
25