ELECTRICAL DATA

Unit Size ---
OPER VOLTS*
V/PH
Voltage,
Series
MIN
24--- 30
208/230
36--- 30
208/230
187
48--- 31
208/230
60--- 31
208/230
* Permissible limits of the voltage range at which the unit will operate satisfactorily
{ If wire is applied at ambient greater than 30_C, consult table 310 ---16 of the NEC (NFPA 70). The ampacity of non ---metallic---sheathed cable (NM), trade
name ROMEX, shall be that of 60_C conditions, per the NEC (NFPA 70) Article 336 ---26. If other than uncoated (no ---plated), 60 or 75_C insulation, copper
wire (solid wire for 10 AWG or smaller, stranded wire for larger than 10 AWG) is used, consult applicable tables of the NEC (NFPA 70).
Length shown is as measured one way along wire path between unit and service panel for voltage drop not to exceed 2%.
}
** Time ---Delay fuse.
FLA --- Full Load Amps
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
RLA --- Rated Load Amps
NOTE: Control circuit is 24 ---V on all units and requires external power source. Copper wire must be used from service disconnect to unit.
All motors/compressors contain internal overload protection.
Complies with 2007 requirements of ASHRAE Standards 90.1

A- -WEIGHTED SOUND POWER (dBA)

Unit Size ---
Standard Rating
Voltage, Series
(dBA)
71 --- low stage
24 --- 30
72 --- high stage
72 --- low stage
36 --- 30
74 --- high stage
74 --- low stage
48 --- 31
74 --- high stage
73 --- low stage
60 --- 31
73 --- high stage
NOTE: Tested in accordance with AHRI Standard 270 ---08. (Not listed with AHRI).
CHARGING SUBCOOLING (TXV- -TYPE EXPANSION DEVICE)
UNIT SIZE --- VOLTAGE, SERIES
24--- 30
36--- 30
48--- 31
60--- 31
CONTROLS / THERMOSTATS
Infinity Controls
SYSTXCCUIZ01---B
Infinity System Zone Control User Interface
SYSTXCCUID01---B
Infinity System Non--- Zone Control User Interface
THERMOSTAT / SUBBASE
PKG.
TP---PRH01---A
TP---NRH01---A
TP---PHP01*
TP---NHP01*
TC ---PHP01*
TC ---NHP01*
*Serial numbers beginning with 2909 and thereafter.
COMPR
MAX
RLA
LRA
10.30
52.0
16.70
82.0
253
21.20
96.0
23.00
118.0
TYPICAL OCTAVE BAND SPECTRUM (dBA, without tone adjustment)
125
250
49.4
61.4
49.9
58.4
48.9
57.9
49.4
59.4
53.9
63.9
52.9
60.9
51.9
58.9
52.4
61.4
Programmable Thermidistat
Non--- programmable Thermidistat
Performance Series Programmable HP Stat
Performance Series Non--- programmable HP Stat
Comfort Series Programmable HP Stat
Comfort Series Non--- programmable HP Stat
MIN
MIN
FAN
WIRE
WIRE
MCA
SIZE{
SIZE{
FLA
60° C
75° C
0.7
13.58
14.00
14.00
1.2
22.08
12.00
12.00
1.3
27.80
10.00
10.00
1.3
30.06
8.00
10.00
500
1000
60.8
61.5
61.8
60.0
64.3
62.0
62.3
64.0
61.8
64.0
61.8
64.0
65.3
61.5
62.3
64.0
REQUIRED SUBCOOLING _F (_C)
DESCRIPTION
DESCRIPTION
5
MAX
MAX
LENGTH
LENGTH
FUSE** or
ft. (m)}
ft. (m)}
CKT BRK
60° C
75° C
60 (18.3)
57 (17.4)
57 (17.4)
54 (16.5)
72 (21.9)
68 (20.7)
93 (28.3)
57 (17.4)
4000
8000
55.5
46.9
56.0
50.4
55.5
50.9
56.5
52.4
56.0
47.9
60.0
48.9
55.0
48.4
56.0
49.9
10 (5.6)
10 (5.6)
10 (5.6)
10 (5.6)
MAX
AMPS
20
35
40
50